AI

The **E5CC-RX2ABM-802** is a high-performance digital temperature controller from Omron’s E5CC series. It is designed for precision thermal management in industrial automation.
---
### 1. Model Breakdown (Nomenclature)
The part number indicates specific hardware capabilities and electronic components inside the device:
| Code Segment | Feature | Description |
| :--- | :--- | :--- |
| **E5CC** | Series | 48 x 48 mm compact digital controller |
| **RX** | Control Output | **Relay Output** (SPST-NO, 250 VAC, 3 A) |
| **2** | Auxiliary Outputs | 2 independent relay alarm outputs |
| **A** | Power Supply | 100 to 240 VAC (Universal AC input) |
| **B** | Input Type | Multi-input (Thermocouple, RTD, or Analog) |
| **M** | Option 1 | Standard terminal block (screw terminals) |
| **802** | Special Code | Typically indicates a specific accessory or specialized default setting |
---
### 2. Key Electronic Components & Interfaces
#### A. The Processor and Display
* **High-Contrast LCD:** Uses a white PV (Process Value) display that is highly visible even in low-light industrial environments.
* **Sampling Loop:** Features a high-speed sampling period of **50 ms**, allowing for rapid PID calculations and response to temperature fluctuations.
#### B. Control Output (The "RX" part)
* **Relay Contact:** This model uses an electromechanical relay for the main control output.
* **Capacity:** Rated for 3 Amps at 250 VAC.
* **Life Expectancy:** Mechanical (10 million operations); Electrical (100,000 operations minimum at rated load).
#### C. Input Stage (Multi-Input)
The internal circuitry includes a universal analog-to-digital converter that supports:
* **Thermocouples:** K, J, T, E, L, U, N, R, S, B, W, or PL II.
* **Platinum Resistance Thermometers (RTD):** Pt100 or JPt100.
* **Analog Current/Voltage:** 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, or 0 to 10 V.
---
### 3. Technical Specifications
| Parameter | Specification |
| :--- | :--- |
| **Supply Voltage** | 100 to 240 VAC, 50/60 Hz |
| **Power Consumption** | Max 5.2 VA (at 100-240 VAC) |
| **Control Method** | ON/OFF or 2-PID (with auto-tuning) |
| **Alarm Outputs** | 2 points (Relay: 3A at 250 VAC) |
| **Setting Method** | Front panel keys or CX-Thermo software |
| **Isolation Resistance** | 20 MΩ min. (at 500 VDC) |
---
### 4. Wiring and Installation Tips
* **Terminals 1 & 2:** Power Supply (100–240 VAC).
* **Terminals 3 & 4:** Control Output (Relay).
* **Terminals 11 & 12:** Sensor Input (ensure polarity is correct for thermocouples).
* **Noise Suppression:** Since this is a relay-output model, it is recommended to use an external RC snubber circuit if you are switching an inductive load (like a solenoid or contactor) to prevent EMF interference with the controller's electronics.
- ⤷
What is the difference between the RX and QX output models in the E5CC series?
- ⤷ How do I perform the auto-tuning function on this controller?
- ⤷ Can this model be integrated into a Modbus RS-485 network?