LC-R067R2P
AI

The **LC-R067R2P** is a specific model of a Valve Regulated Lead Acid (VRLA) battery manufactured by **Panasonic**. It is designed for high reliability and is commonly used in Uninterruptible Power Supplies (UPS), emergency lighting, and medical equipment.
---
### ## Technical Specifications
Below is a breakdown of the electronic characteristics and physical dimensions of the LC-R067R2P.
| Feature | Specification |
| :--- | :--- |
| **Nominal Voltage** | 6V |
| **Nominal Capacity** | 7.2Ah (20-hour rate) |
| **Chemistry** | Lead Acid (VRLA / AGM) |
| **Terminal Type** | Faston 187 (4.75mm) or 250 (6.35mm) |
| **Weight** | Approx. 1.20 kg (2.65 lbs) |
| **Casing Material** | Standard UL94 HB (Optional Flame Retardant) |
---
### ## Internal Electronic Design
The battery utilizes several key design components to manage electricity efficiently:
1. **Absorbent Glass Mat (AGM) Technology:**
The electrolyte is absorbed into a glass fiber mat separator between the plates. This allows the battery to be spill-proof and used in various orientations.
2. **Oxygen Recombination:**
During the charging process, oxygen generated at the positive plate is absorbed by the negative plate, preventing water loss and eliminating the need for maintenance.
3. **Pressure Relief Valves:**
Equipped with one-way safety valves that release excess gas if internal pressure builds up (usually due to overcharging), protecting the structural integrity of the battery.
4. **Lead-Calcium Alloy Grids:**
The plates use a lead-calcium alloy which reduces self-discharge rates and improves the lifespan compared to traditional lead-antimony plates.
---
### ## Charging Parameters
To ensure the longevity of the LC-R067R2P, the following charging voltages must be observed:
* **Cycle Use:** 7.25V to 7.45V (Initial current should be 2.88A or smaller)
* **Standby (Float) Use:** 6.8V to 6.9V
* **Temperature Compensation:** It is recommended to adjust voltage by -10mV/°C (Cycle) or -6mV/°C (Float) for variations from 25°C.
---
### ## Common Applications
* **Backup Power:** Emergency lighting systems and fire alarms.
* **Telecommunications:** Small-scale base station backup.
* **Portable Devices:** Electronic test equipment and power tools.
* **Medical:** Life-support backups and mobile medical carts.
- ⤷