The **M2AC-AD3-R2/CE** is a high-performance, signal-conditioning transducer manufactured by **M-System** (now part of MG CO., LTD.). It is primarily used in industrial automation to convert an AC current input into a standard DC output signal.
---
## 1. Core Technical Specifications
The model number breakdown reveals its primary electronic characteristics:
| Feature | Specification |
| :--- | :--- |
| **Input Signal** | 0 – 5A AC (Standard CT output) |
| **Output Signal** | 4 – 20mA DC |
| **Power Supply** | 100 – 240V AC (Standard) |
| **Isolation** | 3-Way Isolation (Input, Output, Power) |
| **Accuracy** | ±0.3% |
| **Response Time** | ≤ 0.5 seconds (0 to 90%) |
| **Mounting** | DIN Rail |
---
## 2. Key Electronic Components & Design
### A. Input Stage (Current Transformer)
The device contains an internal sensing transformer that steps down the high AC current (0-5A) to a low-voltage level suitable for internal electronic processing. This provides the first layer of galvanic isolation.
### B. Signal Conversion (True RMS vs. Mean Value)
Depending on the specific configuration of the AD3 series:
* **Rectification:** It typically uses a precision rectifier circuit to convert the AC waveform into a proportional DC voltage.
* **Filtering:** Low-pass filters are used to smooth the ripple from the AC-to-DC conversion to ensure a steady 4-20mA output.
### C. 3-Way Isolation Circuitry
This is a critical safety and signal integrity feature. The electronics are divided into three isolated sections:
1. **Input Circuit:** Protected against high-voltage surges from the current transformer.
2. **Output Circuit:** Isolated to prevent ground loops from affecting the PLC or controller.
3. **Power Circuit:** Uses a switching regulator to isolate the mains power supply from the sensitive measurement signals.
### D. Calibration Potentiometers
On the front panel, there are typically two multi-turn trimmers:
* **Zero Adjustment:** Used to calibrate the 4mA floor.
* **Span Adjustment:** Used to calibrate the 20mA ceiling.
---
## 3. CE Marking & Protection
The **/CE** suffix indicates that the electronic components comply with European Directives regarding:
* **EMC (Electromagnetic Compatibility):** The device is shielded against radio frequency interference (RFI) and does not emit excessive electronic noise.
* **LVD (Low Voltage Directive):** Ensures the internal insulation and spacing between components can withstand high voltage without breakdown.
---
## 4. Typical Connection Diagram
```text
[ SOURCE AC LINE ]
|
(CT) 0-5A
|
+-----|-----+
| (1) (2) | <-- Input Terminals
| |
| [M2AC] |
| |
| (4) (5) | <-- Output (4-20mA DC) to PLC
| (7) (8) | <-- Power Supply (100-240V AC)
+-----------+
```
---
- ⤷
What is the maximum allowable load resistance for the 4-20mA output on this model?
- ⤷ Can the M2AC-AD3 handle non-sinusoidal (distorted) waveforms?
- ⤷ How do I perform a field calibration using the Zero and Span trimmers?