AI

The **M2RS-10-R2/CE** is a high-performance, plug-in type **RTD (Resistance Temperature Detector) Transmitter** manufactured by **M-System**. It is designed to take a resistance signal from an RTD sensor (like a Pt100) and convert it into a standard DC output signal (like 4-20mA or 0-10V).
---
### 1. Technical Specifications
| Feature | Specification Details |
| :--- | :--- |
| **Model Series** | M2 (Mini-M) Series |
| **Input Type** | RTD (Pt 100, Pt 50, Ni 508.4, etc.) |
| **Output Type** | Specify code (e.g., A: 4–20 mA, V: 0–10 V) |
| **Power Input (R2)** | 100 – 240 V AC |
| **Accuracy** | ±0.1% of span |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Isolation** | 3-way isolation (input to output to power) |
| **Construction** | Plug-in base socket mount |
---
### 2. Breakdown of the Model Code
The alphanumeric string defines the specific electronic configuration of the unit:
* **M2RS**: Model family (RTD Transmitter).
* **10**: Specifies the input type (Standard Pt 100, 3-wire).
* **R2**: Power supply code (100–240V AC).
* **CE**: Certification mark (Conforms to European Health, Safety, and Environmental standards).
---
### 3. Key Electronic Features
#### A. Three-Way Isolation
The device features galvanic isolation between the **input**, **output**, and **power supply**. This is critical in industrial environments to:
* Prevent ground loops.
* Protect sensitive PLC/DCS inputs from high-voltage surges.
* Reduce electronic noise interference.
#### B. Burnout Protection
The electronic circuit includes a "Burnout" function. If the RTD wire breaks, the transmitter can be configured to drive the output signal to a maximum (Upscale) or minimum (Downscale) value to alert the control system of a sensor failure.
#### C. Linearization
RTD sensors are slightly non-linear. The internal circuitry of the M2RS-10 performs **linearization**, ensuring that the output DC signal is perfectly proportional to the temperature, not just the raw resistance.
---
### 4. Typical Wiring Diagram (Conceptual)
```mermaid
graph LR
A[RTD Sensor] -- 3-wire -- B(Transmitter Input)
C[AC Power 100-240V] -- Power -- B
B -- 4-20mA / 0-10V -- D[PLC / Controller]
```
---
- ⤷
What is the specific output signal code for this model?
- ⤷ How do you calibrate the Zero and Span on this transmitter?
- ⤷ Can this unit be mounted on a standard DIN rail?