M2RTS-R-B2-R2/CE
AI

The **M2RTS-R-B2-R2/CE** is a high-precision, plug-in type RTD (Resistance Temperature Detector) transmitter manufactured by **M-System** (now MG CO., LTD). It is designed to convert signals from a temperature sensor into a standard industrial DC output.
---
### 1. Model Code Breakdown
Understanding the specific electronic configuration through the model suffix:
| Code Segment | Description | Specific Detail |
|:---|:---|:---|
| **M2RTS** | Model Series | RTD Transmitter (Plug-in type) |
| **-R** | Power Input | 24V DC |
| **-B** | Input Signal | Pt 100 (ITS-90) |
| **2** | Output 1 | 4 – 20 mA DC (Load resistance 550 $\Omega$ max) |
| **-R** | Output 2 | 4 – 20 mA DC (Load resistance 550 $\Omega$ max) |
| **2** | Options | Standard (No special coating) |
| **-R2** | Design/Version | Standard Version 2 |
| **-CE** | Certification | CE Marking compliant |
---
### 2. Key Electronic Specifications
The internal circuitry is designed for high isolation and linear signal processing.
* **Input Circuitry:** Designed for a 3-wire Pt 100 sensor. It uses a constant current bridge to sense resistance changes.
* **Isolation:** 4-way isolation (Input to Output 1 to Output 2 to Power).
* **Burnout Protection:** Upscale burnout is standard (the output goes to max if the sensor wire breaks).
* **Response Time:** $\leq$ 0.5 seconds (0 – 90%).
* **Accuracy:** $\pm$0.1% of span.
---
### 3. Connection Diagram (General)
The unit uses a M3 screw terminal base.
| Terminal No. | Function | Description |
|:---|:---|:---|
| 1 | Output 1 (+) | Positive 4-20mA |
| 2 | Output 1 (-) | Negative 4-20mA |
| 3 | Output 2 (+) | Positive 4-20mA |
| 4 | Output 2 (-) | Negative 4-20mA |
| 5 | Input (A) | RTD Terminal A |
| 6 | Input (B) | RTD Terminal B |
| 7 | Input (B) | RTD Terminal B (compensation) |
| 12 | Power (+) | +24V DC |
| 13 | Power (-) | 0V DC |
---
### 4. Installation and Physical Parts
* **Housing Material:** Flame-resistant resin (black).
* **Mounting:** DIN rail or surface mounting via a plug-in socket base.
* **Adjustments:** Front-facing Zero and Span adjustments (multi-turn potentiometers) for field calibration.
- ⤷
How do I calibrate the Zero and Span for this specific model?
- ⤷ What is the maximum allowable resistance for the RTD lead wires?
- ⤷ Can this transmitter be used with a 2-wire RTD sensor?