M2RTS-R-CD-R2/N
AI

The **M2RTS-R-CD-R2/N** is a specific model within the **M2 Series** of signal conditioners manufactured by **M-System** (now part of MG CO., LTD). This device is a compact, plug-in **RTD (Resistance Temperature Detector) Transmitter**.
It is designed to take a signal from an RTD sensor and convert it into a standardized DC output signal (such as 4-20mA or 0-10V) for use in PLCs, DCS systems, or controllers.
---
### 1. Model Code Breakdown
The alphanumeric string defines the specific internal electronic configuration and capabilities:
| Code Segment | Meaning | Specifics for this Model |
| :--- | :--- | :--- |
| **M2RTS** | Model Name | RTD Transmitter (M2 Series) |
| **-R** | Power Input | 24V DC |
| **-CD** | Input Type | Pt 100 (ITS-90) |
| **-R2** | Output Type | 4 – 20 mA DC |
| **-N** | Options | No specific option (Standard version) |
---
### 2. Key Technical Specifications
The electronics are housed in a compact, plug-in base designed for DIN-rail mounting.
* **Accuracy:** Typically $\pm$0.1% of span.
* **Response Time:** $\leq$ 0.5 seconds (0 – 90%).
* **Burnout Protection:** Standard (Upscale burnout). If the sensor wire breaks, the output goes to the maximum limit to alert the system.
* **Isolation:** 3-way isolation (Input to Output to Power). This prevents ground loops and protects sensitive PLC equipment from electrical surges.
* **Temperature Coefficient:** $\pm$0.015% per °C.
---
### 3. Connection and Wiring
The device uses a base socket (typically included) for easy replacement without disconnecting wires.
| Terminal | Function | Description |
| :--- | :--- | :--- |
| **1 & 2** | Output (+) / (-) | The 4-20mA DC signal sent to the controller. |
| **3 & 4** | Power Input | 24V DC supply (+ and -). |
| **5, 6 & 7** | RTD Input | Terminals for 3-wire Pt 100 sensors. |
---
### 4. Electronic Adjustment
On the front of the unit, there are usually two small potentiometers (Trimmers) hidden under a cover:
1. **ZERO:** Used to adjust the 4mA (lower limit) point.
2. **SPAN:** Used to adjust the 20mA (upper limit) point.
---
- ⤷
How do I calibrate the zero and span settings on this specific model?
- ⤷ What is the maximum load resistance for the 4-20mA output?
- ⤷ Can this transmitter support a 2-wire or 4-wire RTD configuration?