The **M2RTS-R-DA-R/UL** is a high-precision, industrial-grade RTD (Resistance Temperature Detector) transmitter. It belongs to the **M2 Series** produced by **M-System** (now part of MG CO., LTD). This specific model is designed to convert signals from a temperature sensor (RTD) into a standard DC output signal.
---
### 1. Model Breakdown
The suffix/model code defines the specific electrical characteristics of the device:
| Code Segment | Meaning | Specification |
| :--- | :--- | :--- |
| **M2RTS** | Model Series | RTD Transmitter (Plug-in base) |
| **-R** | Power Input | 24V DC |
| **-DA** | Output Signal | 4 to 20 mA DC (Source) |
| **-R** | Input Signal | Cu 10 @ 25°C (Copper RTD) |
| **/UL** | Certification | UL/cUL Class I, Division 2 approval |
---
### 2. Key Electronic Components & Features
#### A. Input Section (RTD Interface)
* **Sensor Compatibility:** Designed specifically for **Copper 10 ohm** RTDs.
* **3-Wire Compensation:** It uses a bridge circuit to compensate for lead-wire resistance, ensuring that the distance between the sensor and the transmitter does not affect accuracy.
* **Burnout Protection:** Includes an electronic circuit that drives the output to a specific limit (usually >20mA or <4mA) if the sensor wire breaks.
#### B. Signal Conditioning & Isolation
* **Galvanic Isolation:** This unit features **three-way isolation** (Input to Output to Power). This prevents ground loops and protects sensitive PLC/DCS equipment from high-voltage surges on the field side.
* **Linearization:** Since RTD resistance changes are not perfectly linear with temperature, the internal circuitry applies a linearization curve to ensure the 4-20mA output is proportional to the actual temperature.
#### C. Output Section
* **Current Loop:** Provides a 4-20 mA DC signal.
* **Load Resistance:** Capable of driving loads up to 550 $\Omega$.
---
### 3. Technical Specifications
| Parameter | Specification |
| :--- | :--- |
| **Supply Voltage** | 24V DC (±10%) |
| **Current Consumption** | Approx. 50 mA |
| **Isolation Resistance** | ≥ 100 M$\Omega$ at 500V DC |
| **Dielectric Strength** | 2000V AC @ 1 minute |
| **Accuracy** | ±0.2% of span |
| **Response Time** | ≤ 0.5 seconds (0 – 90%) |
| **Mounting** | Surface or DIN rail (via socket) |
---
### 4. Terminal Connection Diagram (Typical)
```text
[ Power Input ] [ Input (RTD) ] [ Output ]
Term 7: +24V Term 1: A Term 4: +
Term 8: 0V Term 2: B Term 5: -
Term 3: B
```
---
- ⤷
How do I calibrate the Zero and Span on the M2RTS?
- ⤷ What is the difference between the /UL and standard versions of this transmitter?
- ⤷ Can this model be used with a PT100 sensor instead of Copper 10?