M2VF-AA-R2/
AI

The **M2VF-AA-R2** is a high-performance **Mini-M series signal conditioner** (specifically a Voltage/Current Input to Voltage Output transmitter) manufactured by **M-System**. It is designed to galvanically isolate and convert analog signals for industrial automation and control systems.
---
## 1. Technical Specifications
The following table outlines the primary electronic characteristics of the M2VF-AA-R2:
| Feature | Specification |
| :--- | :--- |
| **Model Type** | Ultra-slim Signal Conditioner (Mini-M Series) |
| **Input Signal** | 4 to 20 mA DC (Input resistance 250 Ω) |
| **Output Signal** | 4 to 20 mA DC (Load resistance 600 Ω max.) |
| **Power Input** | 24V DC (Operating range 24V ± 10%) |
| **Isolation** | 3-way isolation (input to output to power) |
| **Accuracy** | ±0.1% of span |
| **Response Time** | ≤ 0.5 seconds (0 to 90%) |
| **Housing Material** | Flame-resistant resin (Black) |
---
## 2. Key Electronic Components & Design
The device is engineered for high reliability in harsh industrial environments. Its electronic architecture focuses on:
### A. Three-Way Isolation
The "R2" designation indicates 24V DC power, but the unit maintains strict galvanic isolation between:
1. **The Input Circuit** (Sensor/Transmitter side)
2. **The Output Circuit** (PLC/DCS/Controller side)
3. **The Power Supply**
*This prevents ground loops and protects sensitive equipment from high-voltage surges.*
### B. Signal Conditioning Circuitry
* **Precision Resistors:** Used to convert the current input into a stable voltage for internal processing.
* **Zero and Span Adjustments:** Located on the front panel, these allow for fine-tuning the electronic calibration (±5%).
* **Active Filtering:** Integrated circuits filter out high-frequency noise and electromagnetic interference (EMI).
### C. Physical Interface
* **Terminal Blocks:** M3 screw terminals for secure electrical connections.
* **DIN Rail Mounting:** The unit is designed to snap onto a standard 35mm DIN rail.
* **LED Indicator:** A power LED indicates the status of the internal DC-DC converter.
---
## 3. Terminal Connection Map
*Note: Always refer to the specific wiring diagram on the side of the unit before installation.*
| Terminal No. | Function | Description |
| :--- | :--- | :--- |
| **1** | Output (+) | Positive Output to Receiver |
| **2** | Output (-) | Negative Output to Receiver |
| **3** | Power (U) | +24V DC Power Supply |
| **4** | Power (V) | 0V DC Power Supply |
| **5** | Input (+) | Positive Input from Source |
| **6** | Input (-) | Negative Input from Source |
---
- ⤷
What are the specific environmental ratings (temperature/humidity) for this model?
- ⤷ How do I calibrate the zero and span settings on the M2VF-AA-R2?
- ⤷ Does this model support HART communication pass-through?