M2VF2-4W2-R/UL
AI

The **M2VF2-4W2-R/UL** is a high-precision, plug-in type signal conditioner (transducer) manufactured by **M-System** (now MG CO., LTD.). It is specifically designed to convert a variable frequency input (from sensors like flow meters or tachometers) into a standard DC output signal.
---
### ## Technical Specifications
The model number breaks down into specific electronic characteristics:
| Component Code | Description | Specifications |
| :--- | :--- | :--- |
| **M2VF2** | Base Model | Variable Frequency Transmitter |
| **4W** | Input Type | Contact, Open Collector, or Voltage Pulse |
| **2** | Output Type | 4 – 20 mA DC (Source) |
| **R** | Power Input | 24V DC |
| **UL** | Standard | UL/cUL Class I, Div 2 Approval |
---
### ### Key Electronic Components & Functionality
#### 1. Input Section (Frequency Detection)
The device is designed to interface with various pulse-emitting sensors.
* **Trigger Levels:** It features adjustable threshold levels to detect pulses from different sources (dry contacts, NPN/PNP, or magnetic pickups).
* **Pulse Width:** It can process pulses with a minimum width of 10 microseconds.
#### 2. Signal Processing (F/V Conversion)
At the heart of the M2VF2 is a **Frequency-to-Voltage (F/V) converter**.
* **Linearization:** It ensures the output is proportional to the input frequency.
* **Frequency Range:** The range is typically field-adjustable (within the specific factory-ordered range) using the "Zero" and "Span" potentiometers on the front panel.
#### 3. Output Section (Current Loop)
The device converts the processed signal into a **4-20mA DC** loop.
* **Load Resistance:** It can drive a load up to 750 $\Omega$.
* **Response Time:** Approximately 0.5 seconds (0 – 90%).
#### 4. Isolation & Protection
* **3-Way Isolation:** Provides electronic isolation between the **Input**, **Output**, and **Power** terminals (up to 2000V AC). This prevents ground loops and protects sensitive PLC/DCS inputs from electrical noise.
* **UL/cUL Certification:** Built with components that meet safety standards for hazardous locations (Class I, Division 2).
---
### ### External Connections (Pin Layout)
The unit uses a standard 8-pin socket base.
| Pin No. | Function | Description |
| :--- | :--- | :--- |
| 1 | Output (+) | 4-20mA Positive |
| 2 | Output (-) | 4-20mA Negative |
| 3 | Input (+) | Frequency Pulse Input |
| 4 | Input (-) | Common |
| 7 | Power (+) | +24V DC |
| 8 | Power (-) | 0V DC |
---
- ⤷