M2VT-B1-R2
AI

The **M2VT-B1-R2** is a high-performance **Programmable Signal Conditioner** (often referred to as a transducer or isolator) manufactured by **M-System**. It is part of the Mini-M series and is designed to convert a DC input signal into a standard DC output signal while providing galvanic isolation.
---
## 1. Technical Specifications
The model number **M2VT-B1-R2** breaks down into specific technical attributes:
| Component Code | Meaning | Specifications |
|:---|:---|:---|
| **M2VT** | Model Series | Programmable Signal Conditioner (Microprocessor-based) |
| **B** | Input Signal | DC Input (Configurable; Factory set to 1–5V DC) |
| **1** | Output Signal | 4–20 mA DC |
| **R2** | Power Supply | 11–27V DC |
### Key Electrical Characteristics
* **Accuracy:** ±0.1% of span.
* **Response Time:** $\leq$ 0.5 seconds (0 to 90%).
* **Isolation:** 2000V AC @ 1 minute (Input to Output to Power to Ground).
* **Insulation Resistance:** $\geq$ 100 M$\Omega$ with 500V DC.
---
## 2. Core Electronic Components & Architecture
The internal circuitry of the M2VT-B1-R2 is built around several critical stages:
### A. Input Stage (A/D Conversion)
The unit features a high-impedance input stage that accepts DC voltage or current. Because it is "programmable," the input signal is processed through an **Analog-to-Digital Converter (ADC)**. This allows the device to handle non-linear signals or apply square root extraction via software.
### B. Microprocessor Control
Unlike simple analog isolators, the M2VT uses a **Microcontroller (MCU)**. This allows for:
* **Zero/Span Adjustments:** Digital calibration without physical potentiometers.
* **User Programming:** Parameters can be changed using a PC or a dedicated hand-held programmer.
### C. Galvanic Isolation (The Optical/Magnetic Barrier)
To prevent ground loops and protect sensitive PLC/DCS inputs, the device employs **Three-way Isolation**:
1. **Input to Output**
2. **Input to Power**
3. **Output to Power**
### D. Output Stage (D/A Conversion)
The processed digital signal is converted back to an analog 4–20mA current loop via a **Digital-to-Analog Converter (DAC)** and a constant-current drive circuit.
---
## 3. Wiring and Terminal Configuration
The device is designed for DIN rail mounting with a plug-in base.
| Terminal No. | Function | Description |
|:---:|:---|:---|
| 1 | Output (+) | 4–20 mA Current Output |
| 2 | Output (-) | Common Return |
| 3 | Input (+) | DC Voltage/Current Input |
| 4 | Input (-) | Input Common |
| 5 | Power (+) | 11–27V DC Supply |
| 6 | Power (-) | 0V DC |
---
## 4. Maintenance and Programming
The M2VT-B1-R2 features a front-facing jack for the **PU-2x** (Programming Unit) or a PC connection. This allows the user to:
* Change the input range.
* Enable/Disable linear characterization.
* Check the current output value for troubleshooting.
- ⤷
How do I calibrate the zero and span settings on the M2VT-B1-R2?
- ⤷ What are the compatible PC configuration software and cables for this model?
- ⤷ Can this unit be used for square root extraction in flow measurement applications?