The **M2VT-B1-R2/K** is a high-performance **V/I Converter (Signal Conditioner)** manufactured by **M-System**. It is designed to convert DC voltage or current input signals into standardized DC voltage or current output signals with galvanic isolation.
Below is a breakdown of its technical specifications and electronic components.
---
## 1. Technical Specifications
| Feature | Specification |
| :--- | :--- |
| **Model Series** | M2VT (Mini-M Series) |
| **Input Signal** | DC Voltage or Current (Configurable) |
| **Output Signal** | DC Voltage or Current (Configurable) |
| **Power Input (R2)** | 11 - 27V DC |
| **Response Time** | $\le$ 0.5 seconds (0 – 90%) |
| **Accuracy** | $\pm$0.1% |
| **Isolation** | 3-Way (Input - Output - Power) |
| **Mounting** | DIN Rail Mounting |
---
## 2. Model Number Suffix Breakdown
The suffix `/K` often denotes a specific customization or coating:
* **M2VT**: Basic model (Signal Conditioner).
* **B1**: Specific input/output range configuration (Often 4-20mA or 1-5V).
* **R2**: 24V DC power supply requirement.
* **K**: Usually indicates **Multi-output** or specific **Fast Response** options depending on the production lot (often refers to a customized gain or response curve).
---
## 3. Electronic Architecture
The device functions through three primary internal stages to ensure signal integrity:
### A. Input Stage
* **Shunt Resistor/Attenuator:** If the input is current, a high-precision shunt converts it to voltage.
* **Surge Absorbers:** Protects the internal circuitry from voltage spikes on the field side.
### B. Isolation & Processing Stage
* **Optical Isolation:** Uses opto-isolators to decouple the input from the output, preventing ground loops.
* **Zero/Span Adjustment:** Contains high-precision potentiometers (accessible on the front) to calibrate the lower and upper limits of the signal.
### C. Output Stage
* **Amplifier Circuit:** Scales the signal to the desired industrial range (e.g., 4-20mA).
* **Drive Circuitry:** Ensures the output can drive the required load impedance (typically up to 600 $\Omega$ for current outputs).
---
## 4. Connection Diagram
| Terminal | Function | Description |
| :---: | :--- | :--- |
| **1 & 2** | Input | Connect to the sensor/source |
| **3 & 4** | Output | Connect to PLC/Controller |
| **5 & 6** | Power Supply | 24V DC (+ / -) |
---
- ⤷
What are the specific input range options for the B1 configuration?
- ⤷ How do I perform a Zero/Span calibration on this unit?
- ⤷ What is the maximum load resistance supported for a 4-20mA output?