The **REB-AC-R/Q** refers to a high-performance speed controller (Governor) typically used for AC motors, such as those found in industrial fans, ventilation systems, and heat recovery units (specifically brands like S&P - Soler & Palau).
### 1. Technical Specifications
The device is designed to regulate the speed of single-phase motors by varying the voltage.
| Component / Parameter | Specification |
| :--- | :--- |
| **Input Voltage** | 230V AC (Single Phase) |
| **Frequency** | 50/60 Hz |
| **Max Current** | Generally 1A to 5A (depending on sub-model) |
| **Protection Rating** | IP44 or IP54 (depending on housing) |
| **Control Method** | Phase Angle Control (Triac-based) |
---
### 2. Core Electronic Components
The internal circuitry of the REB-AC series relies on power electronics to handle high-voltage AC loads.
* **TRIAC (Triode for Alternating Current):**
The "heart" of the device. It acts as a high-speed solid-state switch that chops the AC sine wave to reduce the effective voltage delivered to the motor.
* **Potentiometer:**
The user-facing dial. It adjusts the RC (Resistor-Capacitor) time constant, which determines the "firing angle" of the Triac.
* **DIAC (Diode for Alternating Current):**
Used to trigger the Triac symmetrically, ensuring the motor doesn't hum or vibrate excessively at low speeds.
* **RFI Filter (Inductors and X-Capacitors):**
These parts suppress Radio Frequency Interference. Without them, the high-speed switching of the Triac would cause noise in nearby electronic devices (TVs, Radios).
* **Trimmer (Minimum Speed Adjustment):**
A small internal screw-potentiometer used to set the lowest possible voltage so the motor doesn't stall when the main dial is at its lowest setting.
---
### 3. Functional Differences (R vs. Q)
While sharing the same basic electronics, the letters often denote the physical form factor:
1. **REB-AC-R (Surface Mount):** Usually comes with a full plastic enclosure for wall mounting.
2. **REB-AC-Q (Flush/In-wall):** Designed to be integrated into standard electrical switch boxes, often featuring a cleaner "built-in" aesthetic.
### 4. Wiring and Safety Parts
* **Fuse:** Most models include a ceramic fast-acting fuse to protect the Triac from over-current or short circuits.
* **L / N Terminals:** Standard Line (Brown) and Neutral (Blue) inputs.
* **L1 (Regulated Output):** The terminal that sends the modified voltage to the fan motor.
---
- ⤷
How do I adjust the minimum speed trimmer on a REB-AC controller?
- ⤷ What is the difference between phase-cut dimming and PWM control for AC motors?
- ⤷ What are the common symptoms of a blown Triac in these units?