RXM2AB2JD
AI

### Overview of the RXM2AB2JD
The **RXM2AB2JD** is a high-performance **Miniature Intermediate Relay** belonging to the Schneider Electric *Zelio Relay* (Harmony) range. It is designed to act as an interface between PLC controllers (or other low-power control circuits) and higher-power electrical loads.
---
### Technical Specifications
The following table highlights the core electronic and mechanical parameters of the device:
| Feature | Specification |
| :--- | :--- |
| **Coil Voltage** | 12 V DC |
| **Contact Configuration** | 2 C/O (DPDT - Double Pole Double Throw) |
| **Thermal Current (Ith)** | 12 A at -40…55 °C |
| **Control Type** | Lockable test button |
| **Status LED** | Included (Indicates coil energization) |
| **Mounting Type** | Plug-in (compatible with RXZE sockets) |
| **Switching Voltage** | 250 V AC / 28 V DC |
---
### Key Electronic Components & Features
#### 1. The Control Coil (12V DC)
The "JD" suffix indicates a **12V DC** coil voltage. When current flows through this coil, it creates a magnetic field that moves the mechanical armature to switch the contact states.
* **Average consumption:** ~0.9 W.
* **Drop-out voltage threshold:** $\ge 0.1 Uc$ (1.2V DC).
#### 2. Contact Material and Power
The contacts are typically made of **Silver Alloy (AgNi)**. This provides a balance between conductivity and resistance to "pitting" or welding under electrical arcs.
* **Maximum Switching Power:** 3000 VA (AC) / 336 W (DC).
* **Minimum Switching Capacity:** 170 mW at 10 mA, 17 V.
#### 3. Protection and Indicators
* **LED Indicator:** A built-in green LED lights up when the coil is energized, allowing for quick visual troubleshooting.
* **Mechanical Flag:** A physical indicator shows the position of the contacts.
* **Test Button:** A manual lockable lever allows for testing the circuit without needing to energize the coil.
---
### Pin Configuration (Wiring)
The RXM2AB2JD uses a standardized pin layout for plug-in sockets.
1. **Coil Terminals (A1, A2):** Used to apply the 12V DC control signal.
2. **Common Terminals (11, 21):** The input side of the switches.
3. **Normally Closed (12, 22):** Contacts that are closed when the relay is OFF.
4. **Normally Open (14, 24):** Contacts that close when the relay is ON.
---
### Environmental and Durability Limits
* **Mechanical Durability:** 10,000,000 cycles.
* **Electrical Durability:** 100,000 cycles for resistive loads.
* **Operating Temperature:** -40°C to +55°C.
* **Degree of Protection:** IP40.
- ⤷What are the compatible socket models for the RXM2AB2JD?
- ⤷ How do I choose between a 2 C/O and a 4 C/O relay for my application?
- ⤷ Does this relay require an external flyback diode for DC circuits?