W2SP-1CC-R2/N
AI

The **W2SP-1CC-R2/N** is a specific model within the **W2SP Series** of digital panel meters (often referred to as signal conditioners or indicators) manufactured by **M-System** (now part of MG CO., LTD).
This device is primarily used in industrial automation to convert analog signals into digital readouts and provide alarm outputs.
---
### 1. Part Number Breakdown
Understanding the specific electronic configuration requires decoding the suffix codes:
| Code Segment | Description | Details |
| :--- | :--- | :--- |
| **W2SP** | Series Name | Ultra-slim Signal Conditioner / Digital Indicator |
| **1** | Input Type | DC Current (typically 4–20mA or 0–20mA) |
| **CC** | Output Type | Dual (2) Isolated DC Current Outputs |
| **R2** | Power Supply | 11–27V DC (Standard 24V DC application) |
| **N** | Standards/Options | No specific certifications (Standard configuration) |
---
### 2. Key Electronic Features
#### A. Dual Isolated Output
The "CC" designation indicates that this unit provides two independent, isolated analog current outputs. This is electronically significant because:
* **Galvanic Isolation:** It prevents ground loops between the input sensor and the PLC/DCS.
* **Signal Splitting:** One input signal can be sent to two different receivers (e.g., a local controller and a remote data logger) without signal degradation.
#### B. Display and User Interface
* **LED Display:** It features a 4-digit red LED display to show the process value (PV) directly on the DIN rail or panel.
* **Front Keys:** Three front buttons allow for on-site scaling (e.g., converting 4-20mA to 0-100.0%) and alarm setting adjustments.
#### C. Circuit Protection & Design
* **High Density:** The unit is designed for DIN rail mounting with a slim profile (approx. 18mm - 20mm wide) to save cabinet space.
* **Dielectric Strength:** Usually rated for 2000V AC @ 1 minute (Input to Output to Power to Ground).
---
### 3. Technical Specifications
| Parameter | Specification |
| :--- | :--- |
| **Input Impedance** | Approx. 50 $\Omega$ (for 4-20mA input) |
| **Output Load Resistance** | Max 600 $\Omega$ per output |
| **Response Time** | $\leq$ 0.5 seconds (0 – 90%) |
| **Accuracy** | $\pm$0.1% of span |
| **Mounting** | DIN Rail |
| **Terminal Screws** | M3.5 (Nickel-plated steel) |
---
### 4. Typical Connection Diagram
Internally, the electronics follow this signal path:
1. **Input Stage:** Receives the DC current and filters noise.
2. **A/D Conversion:** Converts the analog signal to digital for the microprocessor.
3. **Processing:** Scales the value for the LED display and calculates output levels.
4. **D/A Conversion & Isolation:** Converts digital values back to two independent analog outputs via optocouplers or magnetic transformers.
---
- ⤷
What is the wiring pinout for the W2SP-1CC-R2/N?
- ⤷ How do I calibrate the zero and span points using the front buttons?
- ⤷ Can this unit be used with a 110V AC power source?