数据搜索系统,热门电子元器件搜索
  Chinese  ▼
ALLDATASHEETCN.COM

X  

ABF3 数据表(PDF) 2 Page - M-System Co.,Ltd.

部件名 ABF3
功能描述  Final Control Elements
PDF  7 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
制造商  MSYSTEM [M-System Co.,Ltd.]
网页  https://www.m-system.co.jp/
标志 MSYSTEM - M-System Co.,Ltd.

ABF3 数据表(HTML) 2 Page - M-System Co.,Ltd.

  ABF3 Datasheet HTML 1Page - M-System Co.,Ltd. ABF3 Datasheet HTML 2Page - M-System Co.,Ltd. ABF3 Datasheet HTML 3Page - M-System Co.,Ltd. ABF3 Datasheet HTML 4Page - M-System Co.,Ltd. ABF3 Datasheet HTML 5Page - M-System Co.,Ltd. ABF3 Datasheet HTML 6Page - M-System Co.,Ltd. ABF3 Datasheet HTML 7Page - M-System Co.,Ltd.  
Zoom Inzoom in Zoom Outzoom out
 2 / 7 page
background image
MODEL: ABF3
ABF3 SPECIFICATIONS
ES-2614 Rev.12 Page 2/7
http://www.m-system.co.jp/
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
■ BUTTONS
Digital display selector (IND): Switches between PV input,
CAS input, MV outout; Manual operation ramp rate,
Retroactive time period, or Transition amp rate
Manual output switching: CAS (cascade)/MAN (manual)
selector ('OUT'); the mode selected before power OFF is
recovered when the power is turned on.
Remote output switching: External contact closure switches
the ABF3 to MAN mode when the CAS/MAN selector is at
CAS position; Not switched with MAN position.
■ FUNCTIONS
Manual status contact: Turns on when manual operation is
available
Manual operation ramp rate: 15 sec./100 %. (Add 0.3 sec.
for the total time required to go from 0 % to 100 %.)
Adjustable up to 30 sec. in 1 sec. increments with front
control buttons
Retroactive time period at switching CAS to MAN: 0 sec.
plus response time. Adjustable up to 30 sec. in 1 sec.
increments with front control buttons
When the loop has been turned to MAN control with remote
outputs switching command, the MV output goes back by
the preset time period and holds the output.
Ramp rate at switching MAN to CAS: 1 sec./100 %.
Adjustable up to 30 sec. in 1 sec. increments with front
control buttons
If the CAS control value at the moment of switching from
MAN to CAS mode is deviated from the MV output value in
MAN control, the ABF3 adjusts the difference gradually in
the preset ramp rate.
Receiving MAN command during transition ramp period, the
ABF3 turns to MAN mode after transition ramp function is
completed.
Isolation: PV input to CAS input to MV output to MAN status
contact output to remote output switching command input
to power
(For /T option, non-isolated between CAS input and MV
output)
■ SCALE PLATE: Flame resistant resin
(replaceable at the front; white scale & characters on black
base)
Scale: Max. 4 characters including decimal point and
negative sign
• Divisions: Min. 21, max. 43.9
• Engineering unit: Max. 4 characters (Unit other than %
also can be specified)
■ LEDs
CAS output LED: Red LED turns on in CAS mode.
MAN output LED: Red LED turns on in MAN mode.
PV LED: Red LED turns on with PV indication at PV input.
Green LED turns on while setting the manual operation
ramp rate.
CAS LED: Red LED turns on with CAS indication at CAS
input.
Green LED turns on while setting the retroactive time
period.
MV LED: Red LED turns on with MV indication at MV output.
Green LED turns on while setting the transition ramp rate.
MODE LED: Red LED turns on with the firmware version
indication.
Green LED turns on but Not Used.
EXTERNAL
FRONT CAS-MAN SELECTOR
CONTACT
CAS
MAN
ON
MAN
MAN
OFF
CAS
MAN
■Recommended solderless terminal
3.3 (.13) max
mm (inch)
BARGRAPH/DIGITAL DISPLAY
■ BARGRAPH: PV input, CAS input or MV output
LED: 55 segments, red, 55.5 mm (2.19") long, 3.0 mm (.12")
wide
■ DIGITAL INDICATOR: PV input, CAS input, MV output;
Setting values for Manual operation ramp rate, Retroactive
time period, or Transition ramp rate are displayed by
switching.
LED: 4 digits, red, 10 mm (.39") high, 24 mm (.94") wide
Decimal point position: One decimal places fixed
Scaling range: -15 to +115.0%
Zero indication: Higher-digit zeros are suppressed.
INPUT SPECIFICATIONS
PV input, CAS input: -15.0 to +115.0 %
■ Remote Output Switching Command Input
Sensing (open): Approx. 5 V DC
ON voltage: ≤ 2.3 V DC (ON resistance: ≤ 100 Ω/ON current:
≥ 2 mA)
OFF voltage: ≥ 0.75 V DC (OFF resistance: ≥ 1 kΩ/OFF
current: ≤ 1.5 mA)
OUTPUT SPECIFICATIONS
MV output: -15.0 to +115.0 %, 0.1 % increments
MV Conformance range: 0 – 100 %
■ Manual Status Contact Output
Rated load: 120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)



Html Pages

1 2 3 4 5 6 7


数据表 下载

Go To PDF Page


链接网址



ALLDATASHEET是否为您带来帮助?  [ DONATE ] 

关于 Alldatasheet   |   广告服务   |   联系我们   |   隐私政策   |   数据表链接    |   链接交换   |   制造商名单
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com