Hardware Specifications
Specification
Description
Backplane Current Load
800 ma @ 5V (from backplane)
Operating Temperature
0 to 60°C (32 to 140°F)
Storage Temperature
–40 to 85°C (–40 to 185°F)
Relative Humidity
5 to 95% (non-condensing)
Shock
30g operational, 50g non-operational
Vibration
5 g from 10150 Hz
LED indicators
Module status, Backplane transfer status,
Application status, Serial activity (debug
port), Ethernet link and activity, and error
LED status
Debug/Configuration port (CFG)
CFG Port (CFG)
RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking
Configuration Connector
RJ45 RS-232 Connector (RJ45 to DB-9
cable shipped with unit)
Application Ports
Ethernet Port (Ethernet
Modules)
RJ45 Connector
Link and activity LED indicators
Functional Specifications
The MVI46-ADM API Suite allows software developers
access to the top layer of the SLC backplane and serial
ports. The MVI46-ADMNET API suite accesses the
Ethernet port and serial ports.
Both APIs can be easily used without having detailed
knowledge of the module's hardware design. The
Ethernet Port API provides access to the Ethernet
network. Applications for the MVI46-ADMNET module
may be developed using industry-standard DOS
programming tools and the appropriate API components.
The MVI46-ADMNET module has three serial ports, two
of which are isolated for field interfaces, and one
Ethernet port.
CFG -- debug/configuration -- RS-232
PRT1 -- Application -- RS-232, RS-422 or RS-485
PRT2 -- Application -- RS-232, RS-422 or RS-485
Ethernet Port
PRT1 and PRT2 are jumper configured for direct or
Multi-drop field communication. The application program
can be written to control the two application ports
independently, allowing maximum flexibility in the
design.
General Protocol Specifications
Allows software developers to access Rockwell
Automation backplane and Serial/Ethernet ports to
communicate with various field devices, without
needing detailed knowledge of the module's
hardware design
API library functions are specified using the C
programming language syntax
The following compiler versions are compatible with
the MVI module API:
o
Digital Mars C++ 8.49
o
Borland C++ V5.02
Operating System – General software DOS 6-XL
Flash ROM program space: 896 KB
RAM program and data space: 640 KB
Compact Flash socket: Supports up to 16G
Microdrive (not supplied)
ADM API Libraries
Each API provides a library of function calls. This library
supports any programming language that is compatible
with the Pascal calling convention.
Initialization – Open and close the API
Debug Port – Debug port user interface
Database – Read and write data to database
Timer – Start and check timers
Backplane – Transfer data over the backplane
LED – Set user LED indicators
Flash – Parse configuration files
Miscellaneous – Configure the console
Additional Products
ProSoft Technology offers a full complement of
hardware and software solutions for a wide variety of
industrial communication platforms.
Compatible products in the inRAx product line also
include:
Generic Ethernet ASCII Interface Module (MVI46-
GEC)
Visit our web site at http://www.prosoft-technology.com
for a complete list of products.
Ordering Information
To order this product, please use the following:
MVI46-ADMNET
'C' Programmable Application
Development Module with Ethernet
To place an order, please contact your local ProSoft
Technology distributor. For a list of ProSoft distributors
near you, go to http://www.prosoft-technology.com
Distributors:
Place your order by email or fax to:
North American / Latin American / Asia Pacific
orders@prosoft-technology.com,
fax to +1 661.716.5101
Europe
europe@prosoft-technology.com,
fax to +33 (0) 5.61.78.40.52
Copyright © ProSoft Technology, Inc. 2000 - 2007. All Rights Reserved.
January 23, 2007



Html Pages

1 2


数据表 下载

Go To PDF Page


链接网址



ALLDATASHEET是否为您带来帮助?  [ DONATE ] 

关于 Alldatasheet   |   广告服务   |   联系我们   |   隐私政策   |   数据表链接    |   链接交换   |   制造商名单
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com