5 / 8 page ![]() MODEL: R3-NM1 R3-NM1 SPECIFICATIONS ES-8354 Rev.24 Page 5/8 https://www.m-system.co.jp/ MODBUS I/O ASSIGNMENT ADDRESS DATA FORMAT NAME Coil (0X) 1 – 1024 Digital Output (discrete output) 1025 Main / Sub Switching Command (valid only with SW3-3 set to ON) Inputs (1X) 1 – 1024 Digital Input (discrete input) 1025 – 1040 Module Status 1041 – 1056 Error Status 1057 – 1072 Data Error Status Input Registers (3X) 1 – 256 I Analog Input 257 – 768 F Analog Input Holding Registers (4X) 1 – 256 I Analog Output 257 – 768 F Analog Output I : Integer, 0 – 10000 (0 – 100%) F : Floating (32-bit data cannot be accessed using floating addresses.) Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation. • Module Status indicates whether individual I/O modules are mounted or not. The bit corresponding to the mounted slot turns to “1,” and the unmounted slot to “0.” • Error Status indicates error status for each module as described below. The bit corresponding to such module turns to “1.” R3-TSx, R3-RSx, R3-US4: Input burnout R3-DA16A: Power input in error or disconnected R3-YSx: Output current error (e.g. load unconnected) R3-PC16A: External power supply in error or disconnected • Data Error Status indicates overrange (R3-US4: out of -10% to +110%; the other types: out of -15% to +115%) status for each module. The bit corresponding to such module turns to “1.” • Main / Sub Switching Commands given to the network modules result as follows: MAIN’ MODULE ‘SUB’ MODULE OUTPUT MODE 1 0 Main bus is used; Red light turns on at RUN LED of the I/O modules. 0 1 Sub bus is used; Green light turns on at RUN LED of the I/O modules. 1 1 Main bus is used; Amber light turns on at RUN LED of the I/O modules. 0 0 Output is invalid; RUN LED of the I/O modules turns off. TRANSMISSION DATA DESCRIPTIONS The DIP SW located at the side of the module speci es each I/O module’s data allocation (occupied data area). For example, when the data areas are assigned as shown below: Module 1 4 Module 2 4 Module 3 4 Module 4 1 Module 5 1 Module 6 1 Module 7 1 Then the I/O data are assigned as in the table below: ADDRESS POSITION Input Registers (3X) Holding Registers (4X) 1 – 4, 257 – 264 Slot 1 5 – 8, 265 – 272 Slot 2 9 – 12, 273 – 280 Slot 3 13, 281 – 282 Slot 4 14, 283 – 284 Slot 5 15, 285 – 286 Slot 6 16, 287 – 288 Slot 7 ADDRESS POSITION Coil (0X) Inputs (1X) 1 – 64 Slot 1 65 – 128 Slot 2 129 – 192 Slot 3 193 – 208 Slot 4 209 – 224 Slot 5 225 – 240 Slot 6 241 – 256 Slot 7 For Coil (0X) and Inputs (1X), addresses 16 times assigned data areas (Data Allocation Type) are allotted with the Data Allocation Type ‘1’ and ‘4.’ With ‘8’ and ‘16,’ 64 (4 × 16) are automatically al- lotted. |
|
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |