MODEL NUMBERS
H12WD4875
H12WD4890
OUTPUT SPECIFICATIONS ➀
Operating Voltage (47-63 Hz) [Vrms]
48-660
48-660
Max. Load Current ➂ [Arms]
75
90
Min. Load Current, [mArms]
150
150
Transient Overvoltage [Vpk]
1200
1200
Max. Surge Current, (16.6ms) [Apk]
1000
1200
Max. On-State Voltage Drop @ Rated Current [Vpk]
1.6
1.6
Thermal Resistance Junction to Case (RθJC) [˚C/W]
.31
.28
Maximum I 2 t for Fusing, (8.3 msec.) [A 2sec]
4150
6000
Max. Off-State Leakage Current @ Rated Voltage [mArms]
1.0
1.0
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] ➁
500
500
Max. Turn-On Time ➃
Max. Turn-Off Time
Power Factor (Min.) with Max. Load
0.5
0.5
INPUT SPECIFICATIONS ➀
Control Voltage Range
4-32 Vdc
Max. Turn-On Voltage
4.0 Vdc
Min. Turn-Off Voltage
1.0 Vdc
Nominal Input Impedance
See Note 5
Typical Input Current
15 mA @ 5 Vdc
GENERAL NOTES
➀ All parameters at 25˚C unless otherwise specified.
➁ Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
➂ Heat sinking required, for derating curves see page 2.
➃ Turn-on time for DC control random turn-on versions is 0.02 msec.
➄ Input circuitry incorporates active current limiter.
• 1200 Volt Blocking
• Panel Mount
• Up to 660 Vac
• Zero Voltage and Random
Turn-On
• SCR Output
SERIES H12WD.
REV. 031802
PAGE 1 OF 3
High voltage relays use IC driven cir-
cuits for switching loads up to 660
VAC. All models come with 1200
Volts blocking.
Type H12WD is a snubberless
(reduced leakage current).
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
Series H12WD
25-125Amp • 480 Vac • AC Output
© 2002 CRYDOM CORP, Specifications subject to change without notice.
H12WD4825
H12WD4850
48-660
48-660
25
50
150
150
1200
1200
250
625
1.6
1.6
1.02
.63
260
1620
1.0
1.0
500
500
1/2 Cycle
1/2 Cycle
0.5
0.5
➄
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle
• Integrated Overvoltage
Protection by Automatic
Self Turn-On (Suffix P)
H12WD48125
48-660
125
150
1200
1750
1.7
.22
12700
1.0
500
0.5
1/2 Cycle
1/2 Cycle
➅
Compliant only.
➅
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506