数据搜索系统,热门电子元器件搜索
  Chinese  ▼
ALLDATASHEETCN.COM

X  

UPL12 数据表(PDF) 2 Page - Tycon Systems, Inc.

部件名 UPL12
功能描述  UPSPro® 600W Outdoor UPS System
PDF  2 Pages
Scroll/Zoom Zoom In 100%  Zoom Out
制造商  TYCONSYSTEMS [Tycon Systems, Inc.]
网页  https://www.tyconsystems.com/
标志 TYCONSYSTEMS - Tycon Systems, Inc.

UPL12 数据表(HTML) 2 Page - Tycon Systems, Inc.

  UPL12 Datasheet HTML 1Page - Tycon Systems, Inc. UPL12 Datasheet HTML 2Page - Tycon Systems, Inc.  
Zoom Inzoom in Zoom Outzoom out
 2 / 2 page
background image
UPL12_24-xxx-600 Spec Rev 1 27-Jan-22
Specifications Subject to Change Without Notice
Page 2
UPL12/24-xxx-600
Specifications
System Ordering:
UPL12/24-100-600 12/24V 600W Backup Power System, 100Ah
UPL12/24-200-600 12/24V 600W Backup Power System, 200Ah
For further information contact:
UPL12/24-100-600
UPL12/24-200-600
Battery Voltage (DC)
12VDC or 24VDC (customer configurable)
Input Voltage (AC)
120/240VAC, 50/60Hz, 5A Max.
Capacities (Amp Hr)
100Ah
200Ah
Avail Storage Capacity (Watt Hr)
1200Whr
2400Whr
Max Output Power
600W
Suggested Maximum Load
450W
Maximum Instantaneous Load
30A 500msec
Battery Type
Maintenance Free,Valve Regulated, Sealed Lead Acid, AGM
Battery Life
5+ years
Battery Cable Fuse
6x32mm 30A 250V Ceramic Fuse
Controller Type
60A MPPT Solar Controller with Status Display and 30A Load with on/off switch
Maximum Solar Panel Size
780W @ 12V Battery Config, 1560W @ 24V Battery Config
Controller Display Status
Battery Voltage, Charging Voltage, Charging Current, Load Current, Temperature
Bulk Charge
14.4V / 28.8V
Float Charge
13.8V / 27.5V
Over-discharge protection
11V / 22V
Over-discharge recovery voltage
12.6V / 25.2V
Controller Self Consumption
<1W
Enclosure Type
Pole/Wall Mount Powder Coat Aluminum
Enclosure Size
21 x 14 x 15" (533 x 356 x 381mm)
Operating Temperature
-40°C to +65°C (-40°F to 149°F)
System Weight (without batteries)
26lbs (12kg)
Battery Weight
2 x 40lbs (18kg)
4 x 40lbs (18kg)
Certifications
Individual components used have CE Certifications.
Warranty
3 Years
Tyconsystems.com
14641 S 800 W
Bluffdale, UT 84065
PH: 801-432-0003
FAX: 801-618-4220
To calculate run time:
Battery Capacity (Ah) / 2 / Load Amps = Estimated Run Time in Hours ---OR---
Storage Capacity (Wh) / 2 / Load Watts = Estimated Run Time in Hours.
Example: Estimated load = 50W and Storage Capacity is 1200Wh.
1200 / 2 / 50 =
12hrs run time.
Note: We divide by 2 because we don’t want to discharge the battery more than 50% in order to
extend its life.



Html Pages

1 2


数据表 下载

Go To PDF Page


链接网址



ALLDATASHEET是否为您带来帮助?  [ DONATE ] 

关于 Alldatasheet   |   广告服务   |   联系我们   |   隐私政策   |   数据表链接    |   链接交换   |   制造商名单
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com