69 / 192 page ![]() — Manual switch-disconnectors OT160...4000, IEC Technical data Technical data according to IEC 60947-3 Switch type OT160EV OT200E OT250E OT315E OT400E OT630E OT800E Rated insulation voltage and rated operational voltage AC-20, DC-20 Pollution degree 3 1 000 V 1 000 V 1 000 V 1 000 V V 1 000 1 000 V 1 000 V Dielectric strength 50 Hz 1 min. 10 kV 10 kV 10 kV 10 kV 10 kV 10 kV 10 kV Rated impulse withstand voltage 12 kV 12 kV 12 kV 12 kV 12 kV 12 kV 12 kV Rated thermal current and rated operational current AC-20, DC-20 In open air 200 A 200 A 250 A 315 A 400 A 630 A 800 A in ambient 40 °C 4) In enclosure 160 A 200 A 250 A 315 A 400 A 630 A 800 A ...with minimum cable cross section Cu 70 mm² 95 mm² 120 mm² 185 mm² 240 mm² 2x185 mm² 2x240 mm² Rated operational current, AC-21A ≤ 500 V 200 A 200 A 250 A 315 A 400 A 630 A 800 A 690 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A 1000 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A Rated operational current, AC-22A ≤ 500 V 200 A 200 A 250 A 315 A 400 A 630 A 800 A 690 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A 1000 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A Rated operational current, AC-23A ≤ 500 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A 690 V 160 A 200 A 250 A 315 A 400 A 630 A 800 A 1000 V 135 A 135 A 135 A 200 A 200 A 400 A 400 A Rated operational current / poles in series, DC-21A 1) 24...110 V 160 A/2 200 A/2 250 A/2 315 A/1 2) 400 A/1 2) 630 A/1 800 A/1 220 V 160 A/2 200 A/2 250 A/2 315 A/2 2) 400 A/2 2) 630 A/1 800 A/1 440 V 160 A/3 200 A/3 250 A/3 315 A/3 360 A/3 630 A/2 800 A/2 660 V 160 A/4 200 A/4 230 A/4 2) 315 A/4 360 A/4 630 A/4 2) 650 A/4 2) Rated operational current / poles in series, DC-21B 800 V 160 A/5 200 A/5 250 A/5 315 A/5 400 A/5 600 A/5 600 A/5 1000 V 160 A/6 200 A/6 250 A/6 315 A/6 400 A/6 600 A/6 600 A/6 Rated operational power, AC-23 3) 230 V 48 kW 60 kW 75 kW 100 kW 132 kW 200 kW 250 kW 400 V 80 kW 110 kW 140 kW 160 kW 220 kW 355 kW 450 kW 415 V 88 kW 110 kW 145 kW 180 kW 230 kW 355 kW 450 kW 500 V 112 kW 132 kW 170 kW 220 kW 280 kW 400 kW 560 kW 690 V 144 kW 200 kW 250 kW 315 kW 400 kW 630 kW 800 kW Rated breaking capacity in category AC-23 ≤ 500 V 1 280 A 1 600 A 2 000 A 2 520 A 3 200 A 5 040 A 6 400 A 690 V 1 280 A 1 600 A 2 000 A 2 520 A 3 200 A 5 040 A 6 400 A Rated conditional short-circuit current Iq(r.m.s.) and corresponding max. allowed cut-off current Îc. The cut-off current Îc. refers to values listed by fuse manufacturers (single phase test acc. to IEC60269) Iq 100kA, 500V Max. OFA_fuse size Îc 40.5 kA 40.5 kA 40.5 kA 61.5 kA 61.5 kA 90 kA 90 kA gG/aM 315 A/315 A 315 A/315 A 315 A/315 A 500 A/450 A 500 A/450 A 800 A/1 000 A 800 A/1 000 A Iq 80kA, 690V Max. OFA_fuse size Îc 40.5 kA 40.5 kA 40.5 kA 59 kA 59 kA 83.5 kA 83.5 kA gG/aM 355 A/315 A 355 A/315 A 355 A/315 A 500 A/500 A 500 A/500 A 800 A/1 000 A 800 A/1 000 A lq 100kA, 690V Max. fuse size gG/aM 250A/250A 250A/250A 250A/250A -/400A -/400A -/630A -/630A Rated short-time withstand current r.m.s. value Icw ≤ 1000 V 0.15 s 15 kA 15 kA 15 kA 31 kA 31 kA 38 kA 38 kA ≤ 1000 V 0.25 s 15 kA 15 kA 15 kA 24 kA 24 kA 36 kA 36 kA ≤ 1000 V 1 s 8 kA 8 kA 8 kA 15 kA 15 kA 20 kA 20 kA Rated short-circuit making capacity Peak value Icm ≤ 1000 V 30 kA 30 kA 30 kA 65 kA 65 kA 80 kA 80 kA Rated capacitor power when no initial charge on the capacitor The capacitor ratings are limited by the fuse links 415 V 80 kVAr 100 kVAr 115 kVAr 145 kVAr 180 kVAr 250 kVAr 310 kVAr 500 V 96 kVAr 120 kVAr 135 kVAr 175 kVAr 215 kVAr 300 kVAr 375 kVAr 690 V 128 kVAr 160 kVAr 190 kVAr 250 kVAr 325 kVAr 450 kVAr 550 kVAr Power loss / pole With rated current 3.2 W 4 W 6.5 W 6.5 W 10 W 25 W 40 W Mechanical endurance Divide by two for oper. cycles 20 000 Oper. 20 000 Oper. 20 000 Oper. 16 000 Oper. 16 000 Oper. 10 000 Oper. 10 000 Oper. Weight without accessories 3-pole switch 1.3 kg 1.3 kg 1.3 kg 2.8 kg 2.8 kg 6.1 kg 6.1 kg Terminal bolt size Metric thread diameter x length M8x25 mm M8x25 mm M8x25 mm M10x30 mm M10x30 mm M12x40 mm M12x40 mm Terminal tightening torque Counter torque required 15-22 Nm 15-22 Nm 15-22 Nm 30-44 Nm 30-44 Nm 50-75 Nm 50-75 Nm Operating torque 3-pole switch disconnector 7 Nm 7 Nm 7 Nm 16 Nm 16 Nm 27 Nm 27 Nm 1) Further ratings on request. 2) Category B. 3) These values are given for guidance and may vary acc. to the motor manufacturer. 4) Acc. to IEC 60947-1, § 6.1.1. ABB SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION 69 ABB SWITCH-DISCONNECTORS – HIGH PERFORMANCE, COMPACT SOLUTION 69 |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |