Specifications
General Notes:
1) Mini-Horn models are Listed for indoor use with a
temperature range of 32° F to 120° F (0° C to 49°
C) and maximum humidity of 85% RH.
2) Rated input voltage (either filtered DC or unfil-
tered full-wave-rectified FWR): 24 VDC MIZ
Series Signals are UL Listed over a voltage range
from 20 VDC to 31 VDC. Check the minimum and
maximum output of the power supply and standby
battery and subtract the voltage drop from the cir-
cuit wiring resistance to determine the applied
voltage to the strobes.
Although UL Testing has verified that these products
function even at 80% of their minimum rating and
11% of their maximum rating, Cooper-Wheelock
strongly recommends that the voltage applied to
these products be within their rated input voltage
range. The application of improper voltage may result
in degraded operation or damage to these products.
Contact Cooper-Wheelock for installation instructions
and general information sheets for these products.
These materials contain important information that
should be read prior to specifying or installing these
products, including:
• Total current required by all devices connected to
system primary and secondary power sources.
• Fuse ratings for notification appliance circuits to
handle maximum inrush or peak currents from all
devices on those circuits.
Wiring Diagram (all models):
Warning: Do NOT loop wires; use “In-and-Out” wiring
method.
Mounting Notes
The mounting options reference the maximum num-
ber of field wires (conductors) that can enter the
backbox used with each mounting option. If these
limits are exceeded, there may be insufficient space
in the backbox to accommodate the field wires and
stresses from the wires could damage the product.
Although the limits given for each mounting option
comply with the National Electrical Code (NEC).
Cooper-Wheelock recommends the use of the larg-
est backbox option shown and the use of approved
stranded field wires, whenever possible, to provide
additional wiring room for easy installation and mini-
mum stress on the product from wiring.
Architect and Engineer Specifications
The notification appliance shall be a Cooper-Whee-
lock MIZ Series audible device or approved equiva-
lent. Notification appliance shall be electronic and
use solid state components. Electromechanical alter-
natives are not approved. Each sound pressure mea-
surement at 10 feet shall be 90 dBA minimum at 24
VDC and 88 dBA minimum at 12 VDC. Operating
voltage is 24 VDC using filtered power or unfiltered
power supply (full-wave-rectified). All models shall
have provisions for standard reverse-polarity type
supervision and IN/OUT field wiring using terminals
that accept 12 to 18 AWG wiring.
• The horn appliances may be installed indoors for
surface or flush mounting. They shall be mounted
on standard electrical hardware, requiring no addi-
tional trimplate or adapter.
Cooper-Wheelock products must be used within their pub-
lished specifications and must be PROPERLY specified,
applied, installed, operated, maintained and operationally
tested in accordance with their installation instructions at
the time of installation and at least twice a year or more
often and in accordance with local, state and federal codes,
regulations and laws. Specification, application, installation,
operation, maintenance and testing must be performed by
qualified personnel for proper operation in accordance with
all of the latest National Fire Protection Association
(NFPA), Underwriters’ Laboratories (UL), National Electri-
cal Code (NEC), Occupational Safety and Health Adminis-
tration (OSHA), local, state, county, province, district,
federal and other applicable building and fire standards,
guidelines, regulations, laws and codes including, but not
limited to, all appendices and amendments and the
requirements of the local authority having jurisdiction
(AHJ).



Html Pages

1 2


数据表 下载

Go To PDF Page


链接网址



ALLDATASHEET是否为您带来帮助?  [ DONATE ] 

关于 Alldatasheet   |   广告服务   |   联系我们   |   隐私政策   |   数据表链接    |   链接交换   |   制造商名单
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com