| 数据搜索系统,热门电子元器件搜索 |
|
ADE7751ARS 数据表(PDF) 15 Page - Analog Devices |
|
|
|||||||||||||||||||||||||||||
ADE7751ARS 数据表(HTML) 15 Page - Analog Devices |
|
15 / 16 page ![]() REV. 0 ADE7751 –15– Table IV. F1–4 CF Max for AC Signals SCF S1 S0 (Hz) (Hz) 10 0 1.7 128 × F1, F2 = 43.52 00 0 1.7 64 × F1, F2 = 21.76 10 1 3.4 64 × F1, F2 = 43.52 00 1 3.4 32 × F1, F2 = 21.76 11 0 6.8 32 × F1, F2 = 43.52 01 0 6.8 16 × F1, F2 = 21.76 11 1 13.6 16 × F1, F2 = 43.52 01 1 13.6 8 × F1, F2 = 21.76 SELECTING A FREQUENCY FOR AN ENERGY METER APPLICATION As shown in Table II, the user can select one of four frequencies. This frequency selection determines the maximum frequency on F1 and F2. These outputs are intended to be used to drive the energy register (electromechanical or other). Since only four different output frequencies can be selected, the available frequency selection has been optimized for a meter constant of 100 imp/kWhr with a maximum current of between 10 A and 120 A. Table V shows the output frequency for several maximum currents (IMAX) with a line voltage of 220 V. In all cases, the meter constant is 100 imp/kWhr. Table V. IMAX F1 and F2 (Hz) 12.5 A 0.076 25 A 0.153 40 A 0.244 60 A 0.367 80 A 0.489 120 A 0.733 The F1–4 frequencies allow complete coverage of this range of output frequencies on F1 and F2. When designing an energy meter, the nominal design voltage on Channel 2 (voltage) should be set to half scale to allow for calibration of the meter constant. The current channel should also be no more than half scale when the meter sees maximum load. This will allow overcurrent signals and signals with high crest factors to be accommodated. Table VI shows the output frequency on F1 and F2 when both analog inputs are half scale. The frequencies listed in Table VI align very well with those listed in Table V for maximum load. Table VI. Frequency on F1 and F2 – CH1 and CH2 S1 S0 F1–4 Half-Scale AC Inputs 00 1.7 0.085 Hz 01 3.4 0.17 Hz 10 6.8 0.34 Hz 11 13.6 0.68 Hz Example 1 If full-scale differential dc voltages of +660 mV and –660 mV are applied to V1 and V2 respectively (660 mV is the maximum differential voltage that can be connected to Channel 1 and Channel 2), the expected output frequency is calculated as follows. Gain = 1, G0 = G1 = 0 F1–4 = 1.7 Hz, S0 = S1 = 0 V1 = +660 mV dc = 0.66 V (rms of dc = dc) V2 = –660 mV dc = 0.66 V (rms of dc = |dc|) VREF = 2.5 V (nominal reference value) Note: If the on-chip reference is used, actual output frequencies may vary from device to device due to reference tolerance of ±8%. Freq Hz Hz = ××× × = 574 0 66 066 1 17 25 068 2 ... . . . (8) Example 2 In this example, if ac voltages of ±660 mV peak are applied to V1 and V2, the expected output frequency is calculated as follows. Gain = 1, G0 = G1 = 0 F1–4 = 1.7 Hz, S0 = S1 = 0 V1 = rms of 660 mV peak ac = 0.66/ √2 V V2 = rms of 660 mV peak ac = 0.66/ √2 V VREF = 2.5 V (nominal reference value) Note: If the on-chip reference is used, actual output frequencies may vary from device to device due to reference tolerance of ±8%. Freq Hz Hz = ××× × ×× = 574 0 66 066 1 17 22 2 5 034 2 ... . . . (9) As shown in these two example calculations, the maximum output frequency for ac inputs is always half of that for dc input signals. Table III shows a complete listing of all maxi- mum output frequencies. Table III. Max Frequency Max Frequency S1 S0 for DC Inputs (Hz) for AC Inputs (Hz) 00 0.68 0.34 01 1.36 0.68 10 2.72 1.36 11 5.44 2.72 Frequency Output CF The pulse output CF (calibration frequency) is intended for use during calibration. The output pulse rate on CF can be up to 128 times the pulse rate on F1 and F2. The lower the F1–4 frequency selected the higher the CF scaling. Table IV shows how the two frequencies are related depending on the states of the logic inputs S0, S1, and SCF. Because of its relatively high-pulse rate, the frequency at this logic output is proportional to the instantaneous real power. As is the case with F1 and F2, the frequency is derived from the output of the low-pass filter after multiplication. However, because the output frequency is high, this real power information is accumulated over a much shorter time. Hence, less averaging is carried out in the digital-to-frequency conversion. With much less averaging of the real power signal, the CF output is much more responsive to power fluctuations (see Figure 2). |
|
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |