5 / 23 page ![]() CS5.244 C-Line 24V, 5A, SINGLE PHASE INPUT 4. DC-INPUT Do not operate this power supply with DC-input voltage. Use the QS5.241 unit instead. 5. INPUT INRUSH CURRENT After turn-on of the input voltage, an active inrush limitation circuit limits the input inrush current. Virtually no input inrush current is generated. The charging current into the EMI suppression capacitors is disregarded in the first microseconds after switch-on. Inrush current max. 38Apeak at 230Vac, +40°C ambient, cold start typ. 30Apeak at 230Vac, +40°C ambient, cold start Inrush energy max. 1A2s at 230Vac, +40°C ambient, cold start Fig. 5-1 Typical input inrush current behavior 1 > 2 2 > 3 > Input: 230Vac Output: 24V, 5A Ambient: +40°C Upper curve: Input current (20A / DIV) Medium curve: Input voltage (200V / DIV) Lower curve: Output voltage (10V / DIV) Time scale: 10ms / DIV Jul. 2015 / Rev. 2.0 DS-CS5.244-EN All parameters are specified at 24V, 5A, 230Vac, 50Hz, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 5/23 |
|
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|