  RZMS-U9T-R Datasheet HTML 1Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 2Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 3Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 4Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 5Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 6Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 7Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 8Page - M-System Co.,Ltd. RZMS-U9T-R Datasheet HTML 9Page - M-System Co.,Ltd. Next Button
Zoom Inzoom in Zoom Outzoom out
 3 / 12 page
background image
MODEL: RZMS-U9
RZMS-U9 SPECIFICATIONS
ES-7605 Rev.13 Page 3/12
http://www.m-system.co.jp/
INSTALLATION
Power consumption
•AC: Approx. 5 VA
•DC: Approx. 1.2 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 520 g (1.15 lb)
PERFORMANCE
Accuracy: See "Input type, Range, Accuracy & Temperature
Coefficient" section.
Cold junction compensation error: (°C)
≤ ±[0.6 +|Ambient Temp. – 25|× 0.04]
(in stable ambient temperature; e.g. ±1.0°C at 15°C and
35°C)
Applicable with balanced terminal temperature.
Error will increase by imbalances caused by direct mounting
of the REM3 to the terminals.
Temp. coefficient: See "Input type, Range, Accuracy &
Temperature Coefficient" section.
Response time (Assuming the fastest reading on Modbus)
•DC of ±1000 mV or narrower ranges or T/C:
≤ [Sampling Time + 0.3 sec.] (0 – 90 %)
•DC of ±3 V or wider ranges:
≤ [Sampling Time + 0.5 sec.] (0 – 90 %)
•RTD or potentiometer:
≤ [Sampling Time + 0.3 sec.] (0 – 90 %)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 Vpeak @1 minute
(input 1 to input 2 to input 3 to input 4 to input 5 to input 6
to input 7 to input 8 to input 9 to input 10 to input 11 to
input 12 to trigger input to alarm output to RS-232-C or RS-
485 or configurator jack to power or FG)
2000 V AC @ 1 minute (power to FG)
Note: Peak value including both AC and DC (e.g. 354 V AC
with 0 V DC).
Though the withstand voltage is limited to 500 Vpeak
between the I/O (analog inputs, trigger input or alarm
output) and the power input, there will be no dielectric
breakdown between the I/O (with or without grounding) and
other terminals even when 2000 V AC is applied across FG
and the power input if the earth terminal is adequately
grounded.
Line noise normal mode rejection: ≥ 100 dB
Magnitude of the effects of normal mode 50/60 Hz noise,
with the most appropriate line noise filter frequency setting.
Each input circuit has a CR filter of sufficient large time
constant so that there will be little effect of line noise such
as 500 mV AC superposed on a thermocouple or ±60 mV
input.
Common mode noise rejection
Magnitude of the effects of voltages applied across the
terminal C and the ground terminal when there is no
potential difference among all the C terminals.
DC: N/A
AC, ±3 V, ±6 V, ±12 V: Approx. 86 dB
AC, other ranges: Approx. 120 dB
Common mode noise rejection between channels:
Magnitude of the effects of DC/50/60 Hz voltages applied
across the terminals C of the present and the last scanned
channels. (Data are scanned from ch 1 to ch 12 in turn and
back to ch 1 again.)
DC, ±3 V, ±6 V, ±12 V: Approx. 100 dB
DC, other ranges: Approx. 120 dB
AC, ±3 V, ±6 V, ±12 V: Approx. 86 dB
AC, other ranges: Approx. 106 dB
High common mode noise between channels may
compromise the accuracies in low millivolts measuring
including thermocouple input.
We recommend that C terminals of each channel be cross-
wired and then connected to the ground terminal to ensure
the measurement of the highest accuracy.
If such configuration is not possible, take special
consideration to minimize the channel-to-channel common
mode noise and the potential against the ground terminal.
The potential of the open terminal C against the ground
terminal equals to that of the last scanned channel. If ch 2
and ch 3 are not connected, the accuracy of ch 4
measurement is affected by potential difference between
the C terminals of ch 1 and ch 4.
STANDARDS & APPROVALS
EU conformity:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
Low Voltage Directive
EN 61010-1, EN 61010-2-201
Installation Category II
Pollution Degree 2
Power input to input or output: Reinforced insulation
(300 V)
RoHS Directive
EN 50581



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12


数据表 下载

Go To PDF Page


链接网址



ALLDATASHEET是否为您带来帮助?  [ DONATE ] 

关于 Alldatasheet   |   广告服务   |   联系我们   |   隐私政策   |   数据表链接    |   链接交换   |   制造商名单
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com