| 数据搜索系统,热门电子元器件搜索 |
|
E5CC-RX2ASM-800 数据表(PDF) 5 Page - Omron Electronics LLC |
|
|
|||||||||||||||||||||||||||||
E5CC-RX2ASM-800 数据表(HTML) 5 Page - Omron Electronics LLC |
|
5 / 36 page ![]() E5CC-800 5 Alarm Outputs Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. *1 With set values 1, 4 and 5, the upper and lower limit values can be set ndependently for each alarm type, and are expressed as “L” and “H.” *2 Set value: 1, Upper- and lower-limit alarm *3 Set value: 4, Upper- and lower-limit range *4 Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No.H174) for information on the loop burnout alarm (LBA). *8 Refer to the E5CC/E5EC Digital Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. Set value Alarm type Alarm output operation Description of function When alarm value X is positive When alarm value X is negative 0 Alarm function OFF Output OFF No alarm 1 Upper- and lower-limit *1 *2 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is outside this deviation range. 2 Upper-limit Set the upward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is higher than the SP by the deviation or more. 3 Lower-limit Set the downward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is lower than the SP by the deviation or more. 4 Upper- and lower-limit range *1 *3 Set the deviation in the set point by setting the alarm upper limit (H) and alarm lower limit (L). The alarm is ON when the PV is inside this deviation range. 5 Upper- and lower-limit with standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit alarm (1). *6 6 Upper-limit with standby sequence A standby sequence is added to the upper-limit alarm (2). *6 7 Lower-limit with standby sequence A standby sequence is added to the lower-limit alarm (3). *6 8 Absolute-value upper-limit The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. 9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. 10 Absolute-value upper-limit with standby sequence A standby sequence is added to the absolute-value upper-lim- it alarm (8). *6 11 Absolute-value lower-limit with standby sequence A standby sequence is added to the absolute-value lower-limit alarm (9). *6 12 LBA (alarm 1 type only) -*7 13 PV change rate alarm - *8 14 SP absolute value upper limit This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). 15 SP absolute value lower limit This alarm type turns ON the alarm when the set point (SP) is smaller than the alarm value (X). 16 MV absolute value upper limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is higher than the alarm value (X). 17 MV absolute value lower limit *9 This alarm type turns ON the alarm when the manipulated variable (MV) is smaller than the alarm value (X). ON OFF PV SP LH SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP LH ON OFF PV SP LH ON OFF PV *5 SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV LH H<0, L>0 |H| < |L| SP Case 1 LH H>0, L<0 |H| > |L| SP Case 2 L H H<0, L<0 SP L H H<0, L>0 |H| ≥ |L| SP L H H>0, L<0 |H| ≤ |L| SP Case 3 (Always ON) LH H<0, L>0 |H| < |L| SP Case 1 LH H>0, L<0 |H| > |L| SP Case 2 L H H<0, L<0 SP L L H H<0, L>0 |H| ≥ |L| SP H H>0, L<0 |H| ≤ |L| SP Case 3 (Always OFF) |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |