| 数据搜索系统,热门电子元器件搜索 |
|
AN4121 数据表(PDF) 21 Page - STMicroelectronics |
|
|
|||||||||||||||||||||||||||||
AN4121 数据表(HTML) 21 Page - STMicroelectronics |
|
21 / 26 page ![]() AN4121 Three-phase systems Doc ID 023243 Rev 1 21/26 If the difference of the readings is computed, which is 1/ √⎯3 times the total three-phase reactive power. This means that the two- wattmeter method can also indicate the total reactive power in the three-phase loads and also the power factor. A.2.2 Three-wattmeter method This method is used in a three-phase four-wire balanced or unbalanced load. The connections are made with one meter in each line as shown in Figure 15. In this configuration, the total active power supplied to the load is equal to the sum of the three wattmeter readings. Figure 15. The wattmeter connections in the three-phase 4-wire loads A.2.3 One-wattmeter method This method is suitable only in three-phase 4-wire balanced loads. The connection of the wattmeter is similar to the drawing given in Figure 15. The total power is equal to three times the reading of only one wattmeter that is connected between one phase and the neutral. () ) 30 cos( I V 30 cos I V P line line 1 12 1 θ + ° = θ + ° = () ) 30 cos( I V 30 cos I V P line line 3 32 2 θ − ° = θ − ° = θ = + = cos I V 3 P P P line line 2 1 Total θ = θ + ° − θ − ° = − sin I V ) 30 cos( I V ) 30 cos( I V P P line line line line line line 1 2 3 2 1 Total P P P P + + = |
|
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |