| 数据搜索系统,热门电子元器件搜索 |
|
ADE7754 数据表(PDF) 24 Page - Analog Devices |
|
|
|||||||||||||||||||||||||||||
ADE7754 数据表(HTML) 24 Page - Analog Devices |
|
24 / 44 page ![]() REV. PrG 01/03 PRELIMINARY TECHNICAL DATA ADE7754 – 24 – No Load Threshold The ADE7754 includes a selectable “no load threshold” or “start up current” feature that will eliminate any creep effects in the active energy measurement of the meter. When enabled, this function is independently applied on each phase’s active power calculation. This mode is selected by default and can be disabled by setting to logic one bit3 of the GAIN register (Address 18h) - see Table X. Any load generating an active power amplitude lower than the mini- mum amplitude specified, will not be taken into account when accumulating the active power from this phase. The minimum instantaneous active power allowed in this mode is 0.005% of the full scale amplitude. As the maximum active power value is 13,743,895d with full scale analog input, the no-load threshold is 687d. For example, an energy meter with maximum inputs of 220V and 40A and Ib=10A, the maximum instantaneous active power is 3,435,974d assuming that both inputs represent half of the analog input full scale . As the no-load threshold represents 687d, the start up current represents 8mA or 0.08% of Ib. Mode selection of the sum of the three active energies The ADE7754 can be configured to execute the arithmetic sum of the three active energies, Wh = WhφA + WhφΒ + WhφC, or the sum of the absolute value of these energies, Wh = |WhφA| + | WhφΒ| + |WhφC|. The selection between the two modes can be made by setting bit2 of the GAIN register (Address 18h) - see Table X. Logic high and logic low of this bit correspond respectively to the sum of absolute values and the arithmetic sum. This selection affects the active energy accumulation in the AENERGY, RAENERGY, LAENERGY registers as well as for the CF frequency output. When the sum of the absolute values is selected, the active energy from each phase is always counted positive in the total active energy. It is particularly useful in 3-phase 4-wire installation where the sign of the active power should always be the same. If the meter is misconnected to the power lines i.e. CT connected in the wrong direction, the total active energy recorded without this solution can be reduced by two third. The sum of the absolute values assures that the active energy recorded represents the actual active energy delivered. In this mode, the Reverse Power information available in the CFNUM register is still detecting when negative active power is present on any of the three phase inputs. LINE ENERGY ACCUMULATION The ADE7754 is designed with a special energy accumula- tion mode which simplifies the calibration process. By using the on-chip zero-crossing detection, the ADE7754 accumu- lates the Active Power signal in the LAENERGY register for an integer number of half cycles, as shown in Figure 29. The line active energy accumulation mode is always active. Important: It is recommended to use this mode with only one phase selected. If several phases are selected, the amount accumulated can be smaller than it is supposed to be. Each one of three phases zero-crossing detection can contrib- ute to the accumulation of the half line cycles. Phase A, B and C zero crossings are respectively taken into account when counting the number of half line cycles by setting to logic one bits 4-6 of the MMODE register. Selecting phases for the Zero crossing counting has also the effect of enabling the Zero-crossing detection, Zero-crossing Time-Out and Pe- riod Measurement for the corresponding phase as described in the Zero-crossing Detection paragraph. The number of half line cycles is specified in the LINCYC register. LINCYC is an unsigned 16-bit register. The ADE7754 can accumulate Active Power for up to 65535 combined half cycles. Because the Active Power is integrated on an integer number of line cycles, the sinusoidal compo- nent is reduced to zero. This eliminates any ripple in the energy calculation. Energy is calculated more accurately because of this precise timing control. At the end of an energy calibration cycle the LINCYC flag in the Interrupt Status register is set. If the LINCYC mask bit in the Interrupt Mask register is enabled, the IRQ output will also go active low. + + Σ LPF1 FROM VA ADC ZEROCROSS DETECT CALIBRATION CONTROL LINCYC[15:0] Σ + + Power Phase A Power Phase B Power Phase C LPF1 FROM VB ADC ZEROCROSS DETECT LPF1 FROM VC ADC ZEROCROSS DETECT ACCUMULATE ACTIVE POWER DURING LINCYC ZERO-CROSSINGS 51 0 51 0 LAENERGY[23:0] WDIV 23 0 MMODE register bit 6 MMODE register bit 4 MMODE register bit 5 Figure 29 - ADE7754 Active Energy Calibration |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |