40 / 81 page ![]() ADT7462 http://onsemi.com 40 Figure 63. How TTHERM Relates to Automatic Fan Control TMIN 0% 100% TTHERM TRANGE HYSTERESIS Step 7—THYST for Temperature Channels THYST is the amount of extra cooling a fan provides after the temperature measured has dropped back below TMIN before the fan turns off. The premise for temperature hysteresis (THYST) is that without it, the fan would merely chatter or cycle on and off regularly whenever the temperature hovers near the TMIN setting. The THYST value chosen determines the amount of time needed for the system to cool down or heat up as the fan is turning on and off. Values of hysteresis are programmable in the range of 1 °C to 15°C. Larger values of THYST prevent the fans from chattering on and off. The THYST default value is set at 4 °C. Hysteresis Register Register 0x60, Bits [3:0] Local HYS Register 0x61, Bits [3:0] Remote 1 HYS Register 0x62, Bits [3:0] Remote 2 HYS Register 0x63, Bits [3:0] Remote 3 HYS In some applications, it is required that fans not turn off below TMIN but remain running at PWMMIN. Bits [1:0] of the PWM1, PWM2 Frequency Register (0x25) and the PWM3, PWM4 Frequency Register (0x26) allow the fans to be turned off or to be kept spinning below TMIN. If the fans are always on, the THYST value has no effect on the fan when the temperature drops below TMIN. Figure 64. THYST Value Applies to Fan On/Off Hysteresis TMIN 0% 100% TRANGE TTHERM THYST Dynamic TMIN Control Mode In addition to the automatic fan speed control mode described in the Automatic Fan Control Overview section, the ADT7462 has a mode that extends the basic automatic fan speed control loop. Dynamic TMIN control allows the ADT7462 to intelligently adapt the system’s cooling solution for best system performance or lowest possible system acoustics, depending on user or design requirements. Use of dynamic TMIN control alleviates the need to design for worst−case conditions and significantly reduces system design and validation time. Designing for Worst−Case Conditions System design must always allow for worst−case conditions. In PC design, the worst−case conditions include, but are not limited to, the following: • Worst−Case Altitude A computer can be operated at different altitudes. Altitude affects the relative air density, which alters the effectiveness of the fan cooling solution. For example, when comparing 40 °C air temperature at 10,000 feet to 20 °C air temperature at sea level, relative air density is increased by 40%. This means that the fan can spin 40% slower and make less noise at sea level than at 10,000 feet while keeping the system at the same temperature at both locations. • Worst−Case Fan Due to manufacturing tolerances, fan speeds in rpm are normally quoted with a tolerance of ±20%. The designer must assume that the fan rpm can be 20% below tolerance. This translates to reduced system airflow and elevated system temperature. Note that fans 20% out of tolerance can negatively impact system acoustics because they run faster and generate more noise. • Worst−Case Chassis Airflow The same motherboard can be used in a number of different chassis configurations. The design of the chassis and the physical location of fans and components determine the system’s thermal characteristics. Moreover, for a given chassis, the addition of add−in cards, cables, or other system configuration options can alter the system airflow and reduce the effectiveness of the system cooling solution. The cooling solution can also be inadvertently altered by the end user. (For example, placing a computer against a wall can block the air ducts and reduce system airflow.) |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |