24 / 36 page ![]() SOFTWARE CONFIGURATION cont. 24 On point for first lead-lag relay Off point for both lead-lag relays On point for second lead-lag relay Figure 16 Lead-lag Relay Configuration Since the configuration for relays in a lead-lag group is the same as alarm relays, refer to page 23 for configuration. The DNRG < Setpoint screen will not be shown since lead- lag relays cannot have the same value for “Relay On” and “Relay Off.” As shown in Figure 16, all the RELAY OFF points in the lead- lag group should be the same value. This allows the lead-lag cycle to reset when more than one relay comes on. The RELAY ON points for the second, third, and fourth relays (if used), are staggered above the RELAY ON point for the first relay. Lead-Lag Relays cont. I/O Configuration Menu (4-20 mA Output Settings) Display Keystroke Comment and/or Additional Keystrokes I/O Config Press ENT Enters the Relay Settings menu. to select Relay Settings Press Scrolls to the 4-20 mA Settings submenu. to select 4-20 mA Settings Press ENT Enters the 4-20 mA Settings submenu. to select Enable/Disable Press ENT, Enables the 4-20 mA output. Press ENT and to proceed to the next item. Disable Controlled by Press ENT or If unit is configured in the Level Only mode, this screen will not be displayed. Level Press to have the 4-20 mA controlled by level, or ENT, , ENT, to have it controlled by volume or flow. 4 mA Point Press ENT Inserts a on the bottom line of the LCD which allows entry of the 4 mA point xxxx units value. After entering the 4 mA value, press ENT and . 20 mA Point Press ENT Inserts a on the bottom line of the LCD which allows entry of the 20 mA point xxxx units value. After entering the 20 mA value, press ENT and . Fault Mode Press ENT Determines the status of the 4-20 mA if a system fault is detected. Use the Hold to select either Hold, 22 mA, or 3.5 mA then press ENT and . Previous Menu Press ENT Reverts back to the 4-20 mA Settings menu. to select The 4-20 mA output can be controlled by either level, vol- ume, or flow depending on which mode was selected in the System Configuration Menu. The RS-485 menu configures the Modbus digital communi- cations port of the unit. 4-20 mA OUTPUT AND RS-485 SETTINGS I/O Configuration Menu (RS-485 Settings) Display Keystroke Comment and/or Additional Keystrokes I/O Config Press ENT Enters the Relay Settings menu. to select Relay Settings Press twice Scrolls to the Communication Port Setup submenu. to select Comm Port Setup Press ENT Enters the Communication Port Setup submenu. to select Address (0-247) Press or ENT This screen is used to set the address for this particular unit during polling. Enter 1 the address via the keypad. Make sure that no other unit uses this same address. Baud Rate Press or ENT Set the baud rate (communication speed) for the unit. Baud rates of 9600, 4800, 9600 2400, or 1200 are available. Enter the baud rate via the keypad. This value must match the Modbus settings of your system. Parity Press or ENT Set the parity bit at Even, Odd, or None via the keypad. This value must match Even the Modbus settings of your system. Previous Menu Press ENT Reverts back to the Communication Port Setup. to select I/O CONFIGURATION MENU cont. |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |