18 / 32 page ![]() 50-604 Kotron Model 804 Sentinel II RF Level Transmitter 15 2.5.7 System Configuration Menu (cont.) Current Menu Location Display Action Comments Run/System Config/ Probe Calibrate Probe Calibrate > to select Access the Probe calibration menu This is the start of the PROBE CALIBRATE menu. Run/System Config/ Probe Calibrate Cal Pt. #1 (LO) > to select Access the lower calibration point menu Run/System Config/ Probe Calibrate/ Cal Point #1 (LO) Initialize > to select Reset the Cal Pt. #1 (LO) to zero The first time the unit is calibrated and when changing “Cal Pt. #1 (LO)”, press ENT. Otherwise press the DOWN arrow. Run/System Config/ Probe Calibrate Enter Password Accept the data entered The “Enter Password” display will not appear if the password has been entered anywhere else in the general program menu. Use the numeric keys to enter your password. Run/System Config/ Probe Calibrate/ Cal Point #1 (LO) Calibrate Calibrate the lower probe reference point Calibrate with the level as low on the probe as possible. There must be at least 1" of level on any insulated probe. The level entered may be the actual level in the vessel or the number of inches of probe coverage. Run/System Config/ Probe Calibrate Previous Menu > to select Press ENT. Run/System Config/ Probe Calibrate Cal Pt. #2 (HI) > to select Access the upper calibration point menu Set up for the upper calibration reference point. Run/System Config/ Probe Calibrate/ Cal Point #2 (HI) Initialize > to select Reset the Cal Pt. #2 (HI) to zero The first time the unit is calibrated and when changing “Cal Pt. #2 (HI)”, press ENT. Otherwise press the DOWN arrow. Run/System Config/ Probe Calibrate/ Cal Point #2 (HI) Enter Password Probe Calibrate Accept the data entered The “Enter Password” display will not appear if the password has been entered anywhere else in the general program menu. Use the numeric keys to enter your password. Run/System Config/ Probe Calibrate/ Cal Point #2 (HI) Calibrate Calibrate the upper probe reference point Calibrate with the level as high on the probe as possible. There must, however, be at minimum 2% (of span) differential between the calibration points. A greater differential will improve accuracy. The level entered may be the actual level in the vessel or the number of inches of probe coverage. Run/System Config/ Probe Calibrate Previous Menu > to select Press ENT. Run System Config Probe Calibrate > to select Press DEL twice to return to the RUN mode. Run Magnetrol Int’l x.x level units Normal operation The RUN mode. |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |