47 / 68 page ![]() ADE7758 Rev. A | Page 47 of 68 Example—Offset Calibration of Phase a Using Pulse Output For this example, ITEST = 50 mA, VNOM = 220 V, VFULLSCALE = 500 V, IFULLSCALE = 130 A, MC = 3200 impulses/kWh, Power Factor = 1, Frequency = 50 Hz, and CLKIN = 10 MHz. With ITEST, VNOM, and unity power factor, the example ADE7758 meter shows 0.009773 Hz on the APCF pulse output and 0.009773 Hz on the VARCF pulse output. This is equivalent to 0.24% for the watt measurement and 0.24% for the VAR measurement. Using Equations 38 through 41, the values 0xFFB and 0xFFA should be written to AWATTOS (0x39) and VAROS (0x3C), respectively. For AWATTOS: 0186 . 0 4 1 2 1 4 6 10 25 = × × = E Q For AVAROS: 014 . 0 4 1 4 2083 202 2 1 4 6 10 24 = × × × = E Q () 5 . 4 – 1 227 0186 . 0 2 00975 . 0 0024 . 0 – 4 = × × × = AWATTOS () 6 – 1 227 014 . 0 2 00975 . 0 0024 . 0 – 4 = × × × = AVAROS Calibration Using Line Accumulation Line cycle accumulation mode configures the nine energy registers such that the amount of energy accumulated over an integer number of half line cycles appears in the registers after the LINECYC interrupt. The benefit of using this mode is that the sinusoidal component of the active energy is eliminated. Figure 80 shows a flow chart of how to calibrate the ADE7758 using the line accumulation mode. Calibration of all phases and energies can be done simultaneously using this mode to save time during calibration. START CAL IRMS OFFSET CAL VRMS OFFSET CAL WATT AND VA GAIN ALL PHASES @ PF = 1 CAL VAR GAIN ALL PHASES @ PF = 0 CALIBRATE PHASE ALL PHASES @ PF = 0.5 CALIBRATE ALL PHASES WATT OFFSET @ IMIN AND PF = 1 CALIBRATE ALL PHASES VAR OFFSETS @ IMIN AND PF = 0 END Figure 80. Calibration Using Line Accumulation Gain Calibration Using Line Accumulation Gain calibration is used for meter-to-meter gain adjustment, APCF or VARCF output rate calibration, and determining the Wh/LSB, VARh/LSB, and VAh/LSB constant. Step 0: Before performing the gain calibration, the CFNUM/CFDEN (0x45/0x46) and VARCFNUM/VARCFDEN (0x47/0x48) values can be set to achieve the correct impulses/kWh, impulses/kVAh, or impulses/kVARh using the same method outlined in Step 4 in the Gain Calibration Using Pulse Output section. The calibration of xWG/xVARG/xVAG (0x2A through 0x32) is done with the line accumulation mode. Figure 81 shows the steps involved in calibrating the gain registers using the line accumulation mode. |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |