| 数据搜索系统,热门电子元器件搜索 |
|
ADM1026JSTZ-R7 数据表(PDF) 20 Page - ON Semiconductor |
|
|
|||||||||||||||||||||||||||||
ADM1026JSTZ-R7 数据表(HTML) 20 Page - ON Semiconductor |
|
20 / 55 page ![]() ADM1026 http://onsemi.com 20 The results of external temperature measurements are stored in 8-bit, twos complement format, as illustrated in Table 8. Table 8. TEMPERATURE DATA FORMAT Temperature Digital Output Hex −128C 1000 0000 80 −125C 1000 0011 83 −100C 1001 1100 9C −75C 1011 0101 B5 −50C 1100 1110 CE −25C 1110 0111 E7 −10C 1111 0110 F6 0C 0000 0000 00 10C 0000 1010 0A 25C 0001 1001 19 50C 0011 0010 32 75C 0100 1011 4B 100C 0110 0100 64 125C 0111 1101 7D 127C 0111 1111 7F Layout Considerations Digital boards can be electrically noisy environments. Take these precautions to protect the analog inputs from noise, particularly when measuring the very small voltages from a remote diode sensor. Place the ADM1026 as close as possible to the remote sensing diode. Provided that the worst noise sources such as clock generators, data/address buses, and CRTs are avoided, this distance can be 4 to 8 inches. Route the D+ and D− tracks close together, in parallel, with grounded guard tracks on each side. Provide a ground plane under the tracks if possible. Use wide tracks to minimize inductance and reduce noise pickup. A 10 mil track minimum width and spacing is recommended. Figure 34. Arrangement of Signal Tracks 10MIL GND D+ GND D– 10MIL 10MIL 10MIL 10MIL 10MIL 10MIL 10MIL 10MIL 10MIL 10MIL Try to minimize the number of copper/solder joints, which can cause thermocouple effects. Where copper/ solder joints are used, make sure that they are in both the D+ and D− paths and are at the same temperature. Thermocouple effects should not be a major problem because 1C corresponds to about 240 mV, and thermocouple voltages are about 3 mV/C of temperature difference. Unless there are two thermocouples with a big temperature differential between them, thermocouple voltages should be much less than 200 mV. Place a 0.1 mF bypass capacitor close to the ADM1026. If the distance to the remote sensor is more than eight inches, the use of twisted-pair cable is recommended. This works from about 6 to 12 feet. For very long distances (up to 100 feet), use shielded twisted pair such as Belden #8451 microphone cable. Connect the twisted pair to D+ and D− and the shield to GND close to the ADM1026. Leave the remote end of the shield unconnected to avoid ground loops. Because the measurement technique uses switched current sources, excessive cable and/or filter capacitance can affect the measurement. When using long cables, the filter capacitor may be reduced or removed. Cable resistance can also introduce errors. A 1 W series resistance introduces about 0.5C error. Limit Values Limit values for analog measurements are stored in the appropriate limit registers. In the case of voltage measurements, high and low limits can be stored so that an interrupt request is generated if the measured value goes above or below acceptable values. In the case of temperature, a hot temperature or high limit can be programmed, and a hot temperature hysteresis or low limit can be programmed, which is usually some degrees lower. This can be useful because it allows the system to be shut down when the hot limit is exceeded, and restarted automatically when it has cooled down to a safe temperature. Analog Monitoring Cycle Time The analog monitoring cycle begins when a 1 is written to the start bit (Bit 0), and a 0 to the INT_Clear bit (Bit 2) of the configuration register. INT_Enable (Bit 1) should be set to 1 to enable the INT output. The ADC measures each analog input in turn, starting with Remote Temperature Channel 1 and ending with local temperature. As each measurement is completed, the result is automatically stored in the appropriate value register. This round-robin monitoring cycle continues until it is disabled by writing a 0 to Bit 0 of the configuration register. Because the ADC is typically left to free-run in this way, the most recently measured value of any input can be read out at any time. For applications where the monitoring cycle time is important, it can easily be calculated. The total number of channels measured is: Five Dedicated Supply Voltage Inputs Ten General-purpose Analog Inputs 3.3 V MAIN 3.3 V STBY Local Temperature Two Remote Temperature |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |