| 数据搜索系统,热门电子元器件搜索 |
|
ADE7932 数据表(PDF) 65 Page - Analog Devices |
|
|
|||||||||||||||||||||||||||||
ADE7932 数据表(HTML) 65 Page - Analog Devices |
|
65 / 120 page ![]() Data Sheet ADE7978/ADE7933/ADE7932 Rev. 0 | Page 65 of 120 POWER FACTOR CALCULATION AND TOTAL HARMONIC DISTORTION CALCULATION POWER FACTOR CALCULATION The ADE7978 provides a direct power factor measurement simultaneously on all phases. Power factor in an ac circuit is defined as the ratio of the total active power flowing to the load to the apparent power. The absolute power factor measurement is defined in terms of leading or lagging, referring to whether the current waveform is leading or lagging the voltage waveform. When the current waveform is leading the voltage waveform, the load is capacitive and is defined as a negative power factor. When the current waveform is lagging the voltage waveform, the load is inductive and is defined as a positive power factor. Figure 83 illustrates the relationship of the current waveform to the voltage waveform. V I ACTIVE (–) REACTIVE (–) PF (+) CAPACITIVE: CURRENT LEADS VOLTAGE INDUCTIVE: CURRENT LAGS VOLTAGE ACTIVE (+) REACTIVE (–) PF (–) ACTIVE (–) REACTIVE (+) PF (–) ACTIVE (+) REACTIVE (+) PF (+) θ = +60° PF = –0.5 θ = –60° PF = +0.5 Figure 83. Capacitive and Inductive Loads As shown in Figure 83, the reactive power measurement is negative when the load is capacitive and positive when the load is inductive. The sign of the reactive power can therefore be used to reflect the sign of the power factor. The ADE7978 uses the sign of the total reactive power as the sign of the absolute power factor. If the total reactive power is in a no load state, the sign of the power factor is the sign of the total active power. Equation 48 shows the mathematical definition of power factor. Power Factor = (Sign Total Reactive Power) × (48) Power Apparent Power Active Total The ADE7978 provides a power factor measurement on all phases simultaneously. These readings are stored in three 16-bit signed twos complement registers: APF (Address 0xE902) for Phase A, BPF (Address 0xE903) for Phase B, and CPF (Address 0xE904) for Phase C. The MSB of these registers indicates the polarity of the power factor. Each LSB of the APF, BPF, and CPF registers equates to a weight of 2−15. Therefore, the maximum register value of 0x7FFF equates to a power factor value of 1, and the minimum register value of 0x8000 corresponds to a power factor of −1. If the power factor is outside the −1 to +1 range (because of offset and gain calibrations), the result is set to −1 or +1, depending on the sign of the fundamental reactive power. By default, the instantaneous total phase active and apparent powers are used to calculate the power factor; the registers are updated at a rate of 8 kHz. The sign bit is taken from the instan- taneous total phase reactive energy measurement on each phase. If a power factor measurement with more averaging is required, the ADE7978 can use the line cycle accumulation measurement on the active and apparent energies to determine the power factor. This option provides a more stable power factor reading. To use the line cycle accumulation mode to determine the power factor, the ADE7978 must be configured as follows: • Set the PFMODE bit (Bit 7) to 1 in the LCYCMODE register (Address 0xE702). • Enable line cycle accumulation mode on both the active and apparent energies by setting the LWATT and LVA bits to 1 in the LCYCMODE register. The update rate of the power factor measurement is now an integral number of half line cycles that can be programmed in the LINECYC register (Address 0xE60C). For complete information about configuring line cycle accumu- lation mode, see the Line Cycle Active Energy Accumulation Mode and Line Cycle Apparent Energy Accumulation Mode sections. Note that the power factor measurement is affected by the no load condition if no load detection is enabled (see the No Load Condition section). If the apparent energy no load condition is true, the power factor measurement is set to 1. If the no load condition based on total active and reactive energies is true, the power factor measurement is set to 0. |
|
链接网址 |
| ALLDATASHEET是否为您带来帮助? [ DONATE ] |
关于 Alldatasheet | 广告服务 | 联系我们 | 隐私政策 | 数据表链接 | 链接交换 | 制造商名单 All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |